Question
Minimum air gap for fixtures not affected by sidewalls
Question
Minimum air gap for fixtures affected by sidewalls
Question
Airgap less than 25mm shall only be approved if tested with vacuums of mercury from 0 to ____
Question
Minimum distance of Atmospheric Vacuum Breaker (AVB) above all downstream piping and floor level rim of receptor
Question
Mininum space clearance between the lowest portion of the assembly and the grade, floor or platform for access and clearance
Question
Minimum temperature of the AVB critical pevel above overflow rim of a water closet bowl or the highest part of a urinal
Question
Minimum height of the AVB critical level above the overflow rim of a water closet bowl or the highest part of a urinal
Question
Mininum distance of Double Check Valve (DC) assembly above all downstream piping and floor level rim of receptor
Question
Elevation of installations above the floor or grade to be provided with a permanent platform.
Question
Minimum airgap for water distribution, or a mininum of 2x diameter
RNPCP Chapter 6 to 9
Score
0 / 10
Correct rate
0%
Correct: 0
Incorrect: 0
Unanswered: 10
Question list
1
Minimum air gap for fixtures not affected by sidewalls2x diameter
2
Minimum air gap for fixtures affected by sidewalls3x diameter
3
Airgap less than 25mm shall only be approved if tested with vacuums of mercury from 0 to ____63.5cm
4
Minimum distance of Atmospheric Vacuum Breaker (AVB) above all downstream piping and floor level rim of receptor150mm or 6"
5
Mininum space clearance between the lowest portion of the assembly and the grade, floor or platform for access and clearance30.5cm
6
Minimum temperature of the AVB critical pevel above overflow rim of a water closet bowl or the highest part of a urinal43.3°C (110°F)
7
Minimum height of the AVB critical level above the overflow rim of a water closet bowl or the highest part of a urinal152mm
8
Mininum distance of Double Check Valve (DC) assembly above all downstream piping and floor level rim of receptor30.5cm
9
Elevation of installations above the floor or grade to be provided with a permanent platform.1.52m or 5'
10
Minimum airgap for water distribution, or a mininum of 2x diameter25mm
11
Mininum height of ballcock's critical level above the full opening of the overflow pipe25mm
12
Mininum installation height of listed non removable hose bibb type backflow preventer above the highest point of usage.152mm
13
Size of iron cast fittings to be galvanized when used in water piping51mm or smaller
14
Maximum lead content for water pipes and fittings8%
15
Number of mesh per 25mm for gravity tanks vent screen14 to 18
16
Inadequate water pressure is less than:103kPa
17
Excessive water pressure is more than:551kPa
18
Percentage of reduced pressure used for all pipe size determination80%
19
Maximum pressure setting for pressure relief valve1033 kPa
20
Height of the drain pipe of pressure relief valve above the ground and pointing downward152mm to 600mm
21
Distance between bottom of water pipe and top of the sewer or drain line0.30m
22
Horizontal distance between the water line and the sewer or drain line0.30m
23
Distance between sewer or drainage piping and water pipes crossing above such pipes0.30m
24
Maximum distance of unions away from regulating equipment, water heater, conditioning tank, or similar.0.30m
25
Maximum intervals of piping supports4' or 1219mm
26
Support trap arms more than _____ in length shall be as close as possible3' or 914mm
27
Closet rings shall be tightly fastened up to the floor with top surface _____ above finish floor.1/4"
28
Mininum size of water service pipe19mm
29
Minimum size of building supply and branches13mm
30
Minimum clearance of galvanized wrought iron or galvanized steel pipe above ground152mm or 6"
31
Minimum depth of vitrified clay pipes or fittings below the ground0.3m
32
Allowable grades for the threads of drainage fittings2%
33
Fixture rating of clotheswasher in groups of 36 FU
34
Fixture unit rating for every 0.063 L/s (1gpm) of contiuous flow from sump pump or ejector2 FU
35
Intervals of cleanouts on each run of piping15m
36
Length of horizontal drain line where cleanouts maybe omitted, except in lines serving sinks or urinals.< 1.5m
37
Slope of horizontal drainage pipe where cleanouts may be omitted72° or less
38
Aggregate offset angle to be provided with an additional cleanout135° or more
39
Front clearance for cleanouts 51mm or less305mm or 12"
40
Front clearance for cleanouts more than 51mm450mm or 18"
41
Vertical clearance from the means of access for cleanouts installed in underground piping0.45m
42
Horizontal clearance from the means of access for cleanouts installed in underground piping0.75m
43
Maximum distance of underfloor cleanout from an access door, trap door or crawl hole.6.1m
44
Minimum size of pump discharge pipe from a sump having a water closet51mm or 2"
45
Minimum distance of the invert of the lowest inlet above the high water or starting level of sumps and receiving tanks51mm or 2"
46
Minimum size of vent for sumps and receiving tanks51mm or 2"
47
Minimum air pressure to be maintained for each meter of height the sewage is raised3 kg/m
48
Distance within the vertical to horizontal change of a stack containing suds producing fixtures where no drainage connection shall be made2.4
49
Number of water closets or 6 fixture unit traps allowed on any vertical stack4
50
Number of water closets or 6 fixture unit traps allowed on any horizontal branch or drain3
51
Minimum diameter of individual vent, or not less than 1/2 of the diameter of the drain32mm or 1 1/4"
52
Fraction of the total permitted length of any vent allowed to be installed in a horizontal position1/3
53
Length of indirect waste pipe to be directly trapped but no need to be vented1.5m to 4.6m (5' to 15')
54
Length of indirect waste pipe if diameter is less than the drain outlet or tailpiece<4.6m
55
Minimum diameter of indirect waste pipe13mm or 1/2"
56
Extension of standpipe receptor of clotheswasher above its pipe0.45m to 0.8m (16" to 30")
57
Height of trap of clotheswasher standpipe receptor above the floor0.15m to 0.45m (6" to 16")
58
Maximum temperature allowed for water to be discharged under pressure directly into the drainage system60°C (140°F)
59
For condensers and sumps, the extension of the deep seal trap within the bottom of the trap152mm (6")
60
For condensers and sumps, diameter of the opening serving as siphon breaker at the top of the deep seal trap.19mm (3/4")
61
Outlets shall be taken off from the side in a manner to allow a water line to be maintained that permanently occupies not less than ___ the capacity of the condensers or sump.1/2
62
Minimum thickness of walls and bottom of sumps, condensers or intercepting tanks constructed of concrete102mm (4")
63
Minimum thickness of plaster on the inside walls of sumps and condensers, etc13mm (1/2")
64
Minimum thickness of metal condensersGA 12 (2.77mm)
65
Sumps and condensers shall contain a volume of not less than twice the volume of water removed from the boiler connected thereto when the normal water level is reduced not less than ___102mm (4")
66
Minimum thickness of chemical-resistant glass lined pipe, high silicon iron pipe or lead pipe receiving acid or corrosive chemicals.3.2mm
67
Minimum area of CW & VS vent1/2 the area of drain
68
Fixture unit limit for wet venting2FU
69
Maximum number of fixtures can be served by a vertical wet vent.4
70
Minimum size of wet vent1 pipe size larger or 51mm
71
Connection of the returned vent for island fixtures to the horizontal drain above the flood level rim152mm (6")
72
In CW & VS, length of branch that must be separately vented.more than 4.6m
73
Minimum size of waste pipe and trap in any CW & VS, in reference to the sizes required and tailpiece size2 pipe size larger
74
Maximum length of tailpiece0.6m
75
Cleanouts may not be required on any wet-vented branch serving a single trap when the fixture tailpiece or connection is larger than ___51mm (2")
76
1 inlet serving not more than 2.8 cu.m refrigeration space32mm (1 1/4")
77
1 inlet serving 4-12 cu.m of refrigeration space51mm (2")
78
1 inlet serving 13-36 cu.m of refrigeration space76mm (3")
79
Minimum rise of each vent above the highest flood level rim before offsetting horizontally to join the vent stack or stack vent152mm (6")
80
Increase in size of vent stack above the reconnection point of stack and horizontal vent1 pipe size
81
Minimum extension of a vent pipe above the roof or firewall0.15m or 6"
82
Minimum clearance of a vent through the roof from any vertical surface nearby.0.30m or 12"
83
Horizontal distance of a vent opening away from any openable window, door opening, air intake, or vent shaft3m
84
Vertical distance of a vent opening above any openable window, door opening, air intake, or vent shaft0.90m or 3'
85
Horizontal distance of a vent opening away from any lot line, alley, and street boundary lines0.90m or 3'
86
Horizontal distance of a vertical vent away from any part of the roof that is used for other purposes3m
87
Vertical extension of a vent above any roof that is used for other purposes.2.1m
88
Each soil or waste stack which extends _____ or more stories above the building drain shall be served by a parallel vent stack10
89
Intervals of yoke ventevery 5 floors
90
Yoke vent connection with the vent stack above the floor levelnot more than 1m
91
Minimum size of an individual vent32mm or 1 1/4"
92
Minimum size of an individual vent but not less than 32 mm1/2 the diameter
93
Fraction of the total permitted length of any vent allowed to be installed in a horizontal position1/3
94
May be served by a common vertical vent2 fixtures