Question
Number of single compartment sinks or laundry tubs of the same depth, or lavatories that can be served by one trap
Question
Maximum center-to-center distance of adjacent fixtures being served by a single trap
Question
Maximum length of tailpiece
Question
Minimum horizontal distance of a trap arm to vent
Question
Trap arm change of direction without requiring a cleanout
Question
For trap arms 75 mm Ø and larger, the change of direction not requiring a cleanout
Question
Maximum developed length between the trap of a water closet from the top of closet ring to inner edge of vent
Question
Minimum thickness of exposed and readily accessible drawn brass tubing trap
Question
Maximum number of slip joints that may be used on the outlet side of a trap
Question
Depth of trap seals
RNPCP Chapter 10 to 13
Score
0 / 10
Correct rate
0%
Correct: 0
Incorrect: 0
Unanswered: 10
Question list
1
Number of single compartment sinks or laundry tubs of the same depth, or lavatories that can be served by one trap3
2
Maximum center-to-center distance of adjacent fixtures being served by a single trap0.75m
3
Maximum length of tailpiece0.6m
4
Minimum horizontal distance of a trap arm to vent2x trap diameter
5
Trap arm change of direction without requiring a cleanout> 90°
6
For trap arms 75 mm Ø and larger, the change of direction not requiring a cleanout< 22 1/2°
7
Maximum developed length between the trap of a water closet from the top of closet ring to inner edge of vent1.8m
8
Minimum thickness of exposed and readily accessible drawn brass tubing trapGA 17 (1.1mm)
9
Maximum number of slip joints that may be used on the outlet side of a trap1
10
Depth of trap seals2" to 4"
11
Minimum water seal for sand interceptors and similar clarifiers152mm
12
Rate of flow of an individual grease trap1.3 to 3.4 L/s
13
The total capacity of fixtures discharging into a grease trap shall not exceed _____ times the flow rate of the grease trap2 1/2
14
Maximum number of fixtures connected to one grease trap4
15
Maximum horizontal distance between the fixture outlet and the grease trap, so grease trap may serve as fixture trap1.2m
16
Maximum vertical tailpiece or drain between the fixture outlet and the grease trap, so grease trap may serve as fixture trap.0.75m
17
Minimum water seal for grease trap51mm or 2"
18
Size of solids to be screened from laundry discharge by means of removable wire basket12.7mm or larger
19
Minimum outlet size of a sand interceptor76mm or 3"
20
Minimum net opening dimension of the inlet section of a sand interceptor0.2 sq.m
21
The minimum depth of sand interceptor under the invert of the outlet pipe610mm or 24"
22
Increase in the area of inlet section for each 18.9 LPM or fraction thereof over 75.7 LPM0.09 sq.m
23
Minimum area of sand interceptor outlet section50% of the inlet section
24
Distance of trap to vent for 32mm Ø762mm or 30" or 2.5'
25
Distance of trap to vent for 38mm Ø1067mm or 42" or 3.5'
26
Distance of trap to vent for 51mm Ø1524mm or 60" or 5'
27
Distance of trap to vent for 76mm Ø1829mm or 72" or 6'
28
Distance of trap to vent for 102mm Ø and larger3048mm or 120" or 10'
29
Maximum developed length between water closet and vent1829mm or 6'
30
Minimum thickness of galvanized sheet metal for rainwater downspout or conductorGA 26 (0.40mm)
31
Rainwater piping commencing ____ from the exterior of a building may be suitable approved materials0.6m or 2'
32
Extension of roof drain strainers above the surface of the roof102mm or 4"
33
Minimum total net inlet area of roof drain with dome-type strainers1.5x area of the outlet
34
Minimum total net inlet area of drain with roof deck strainers2x area of the outlet
35
Rainfall intensity normally used around Manila area102mm/hr
36
Additional for area of 1 wall50%
37
Additional for area of 2 adjacent walls35%
38
Additional for area of 2 opposite wallsno additional area
39
Minimum diameter of building sewer, but not less than size of the building drain152mm or 6"
40
When gutter has semi-circular bottom, the depth of equivalent area of rectangular gutter0.392x diameter
41
When gutter has semi-circular bottom, width of equivalent area of rectangular gutter0.8862x diameter
42
The sizing data for vertical conductors, leaders, and drains is based on the pipes flowing ____ full7/24
43
Ratio of the side dimension of a rectangular vertical piping3:1
44
Public sewer is not available if more than61m
45
Minimum diameter of building sewer, but not less than the size of the building drain152mm or 6"
46
Recommended slope for building sewer2%
47
Allowable slope for drainage piping 102 mm or 152.4mm in diameter given the site constraints1%
48
Allowable slope for drainage piping 203 mm or larger in diameter0.5%
49
Distance of the building sewer from the outer face of any building foundation or wall0.6m or 2'
50
Minimum depth of building sewer below the finish surface of the ground0.3m or 1'
51
Aggregate offset angle to be provided with an additional cleanout135°
52
Length of building sewer not requiring for a cleanout< 3m
53
Maximum distance between manholes91m
54
Distance between bottom of water pipe and top of the sewer or drain line0.3m or 1'
55
Horizontal distance between the water line and the sewer or drain line0.3m or 1'
56
Distance between sewer or drainage piping and water pipes crossing above such drainage pipes0.3m or 1'
57
Minimum distance of water pipe joints away from a sewer line3m or 10'
58
Distance within the property line where every abandoned building sewer shall be plugged or capped1.5m or 5'
59
Maximum number of days from the time of connection to the public sewer an abandoned disposal facility shall be filled30 days
60
Minimum horizontal distance of a building or structure from the building sewer0.6m or 2'
61
Minimum horizontal distance of water supply wells from the building sewer15.2m
62
Minimum horizontal distance of streams from the building sewer.15.2m
63
Minimum horizontal distance of on-site domestic water service line from the building sewer0.3m or 1'
64
Minimum horizontal distance of public water main from the building sewer0.3m or 1'
65
Allowable reduction from water supply wells when constructed of approved materials for use within a building instead of 15.2m7.6m
66
Maximum/Minimum FU on 152mm building sewer @ 2%no minimum
67
Maximum/Minimum FU on 203mm building sewer @ 2%3900/275
68
Maximum/Minimum FU on 254mm building sewer @ 2%6800/300
69
Maximum/Minimum FU on 305mm building sewer @ 2%11200/235
70
Minimum depth to be filled with molten pig lead25.4mm
71
Extension of the finished joint below the rim of the hub3.2mm
72
Minimum wall thickness of threaded plastic pipeSchedule 80
73
Minimum thickness of exposed wiped surface on each side of a wiped joint, and at least as thick as the material being joined19mm
74
Maximum lead content allowable for solders and fluxes in potable water piping2%
75
Job-Fabricated female screwsSchedule 80
76
Enlargement of closet bend from _____ shall be considered an obstruction76mm to 102mm
77
Minimum width of continuous and indelibly colored stripe marking for hard drawn copper tubing6.4mm
78
Green Copper TubingType K
79
Blue Copper TubingType L
80
Red Copper TubingType M
81
Yellow Copper TubingType DMV
82
Minimum weight and thickness of sheet lead for lead safe pans19.56 kg/sq. m.; 1.6 mm thick
83
Minimum weight and thickness of sheet lead for flashing or vent terminals14.63 kg/sq. m.; 1.2 mm thick
84
Minimum wall thickness of lead bends and lead traps3.2mm
85
Approximate diameter of closet rings or flanges178mm or 7"
86
Width of closet ring or flange38mm or 1 1/2"
87
Minimum thickness of caulked-on closet rings or flanges6.4mm
88
Minimum overall depth of caulked-on closet rings or flanges51mm or 2"
89
Number of bolts per water closet4
90
Slope of threaded-type drainage fittings2%
91
Sizes of valves that shall have cast iron bodies102mm or larger
92
Sizes of valves that shall have cast brass or bronze bodiesless than 102mm
93
Sizes of valves that shall be brass and bronze metalup to 51mm