    This type of ground surface generate more rainwater runoff

    concrete sidewalk

  • 2

    What is the minimum condensate pipe diameter of a cooling equipment with capacity through 125 ToR?

    38 mm

  • 3

    The principal artery of the venting system to which vent branches are connected.

    Main Vent

  • 4

    The side walls of a Septic Tank shall be at least ____ above the liquid depth.

    9"

  • 5

    The extension of a soil or waste stack above the highest horizontal drain connected to the stack.

    Stack Vent

  • 6

    Maximum horizontal distance of the trap arm with a diameter of 38 mm

    1.07 m

  • 7

    What is the estimated sewage flow rate of bowling alleys with snack bar only?

    283.9 LpD per lane

  • 8

    Minimum water seal of a grease trap

    51 mm

  • 9

    Wet venting is limited to _____ fixtures

    4

  • 10

    Prohibited vent pipe material below ground

    Galvanized wrought iron

  • 11

    A water that stands in or passes through the ground

    Ground water

  • 12

    All condensers and sumps shall be properly trapped at the outlet with a deep seal trap extending to within ____ of the bottom of the tank.

    6"

  • 13

    Maximum length of a tailpiece

    0.6 m

  • 14

    What is the maximum length allowed for a vent stack serving 48 DFU?

    55

  • 15

    Which among the choices is a prohibited trap?

    Crown trap

  • 16

    A group vent pipe that connects to the vent stack

    circuit vent

  • 17

    The minimum depth of the sand interceptor under the invert of the outlet pipe is _____.

    610 mm

  • 18

    What is the minimum distance from disposal field to another disposal field?

    1.2 m

  • 19

    In a granule test of a water closet, the initial flush of three different flushes must result in no more than _____ on average remaining in the bowl.

    125

  • 20

    The size of a vent pipe is determined by _____.

    FU and length

  • 21

    Determine the size of horizontal rainwater piping with a slope of 2% for a 350 sqm roof in an area where the the rainfall is 102 mm/hr.

    127 mm

  • 22

    Maximum number of slip joint fitting that may be used on the outlet side of a trap

    1

  • 23

    Elastomeric gasketed and rubber-ring joints shall comply with _____ installation standard

    IAPMO

  • 24

    Water closets that are made to accommodate overweight and obese people

    Bariatric Water Closet

  • 25

    Normally in Manila, the rainfall intensity used is _____.

    102 mm

  • 26

    The maximum trap loading of a pipe size 76 mm

    6

  • 27

    Minimum dimension of a sand interceptor's inlet opening

    0.2 sqm

  • 28

    If the development is mostly built of concrete flooring, how can this affect the stormwater sizing?

    the drains might be larger

  • 29

    If a septic tank can have an effective capacity of 4000 L, how much does the secondary compartment hold?

    1,333 L

  • 30

    _____ are recommended for oil handling piping works

    Neoprene gaskets

  • 31

    When disposal fields and/or seepage pits are installed in sloping ground, the minimum horizontal distance between any part of the leaching system and ground surface shall be _____.

    15 feet

  • 32

    What is the storage factor for self-service auto washers?

    1.5

  • 33

    What is the gauge pressure to be maintained for air tests as substitute for water test in water pipings?

    344.5 kpa

  • 34

    Minimum spacing between trenches or leaching beds

    1.20 m

  • 35

    What is the sewage that turns dark and smell unpleasantly due to anaerobic decomposition?

    septic

  • 36

    What is required when a soil or waste stack extends 10 or more stories?

    Parallel vent stack

  • 37

    What downspout size would you specify for a 800 sqm roof with a rainfall intensity around the area of 152.4 mm/hr?

    152 mm

  • 38

    What will be the size of 0.5% sloped circular bottom gutter serving a roof area of 180 sqm, and the rainfall intensity around the area is 76 mm/hr?

    178 mm

  • 39

    What is an underground drain pipe that receives only subsurface or seepage water and convey it to a sump for disposal by gravity flow or by lift pump?

    subsoil drain

  • 40

    What is the horizontal distance required of a vent pipe from any openable window, door opening, air intake, or vent shaft?

    3 m

  • 41

    Connects directly with an individual trap underneath or behind the fixture

    Backvent Pipe

  • 42

    Vertical vent pipes installed in a roof used for other purposes shall extend a minimum of _____ above such roof.

    2.1 m

  • 43

    Every abandoned building sewer shall be plugged or capped within _____ of the property line

    1.5 m

  • 44

    Rainwater piping located within a medium height building basement area shall be of Galvanized Iron, _____.

    Schedule 30

  • 45

    Minimum distance of a 32 mm trap arm diameter to a vent

    64 mm

  • 46

    Which of the following may be true about the sovent system?

    it has lesser maintenance cost

  • 47

    In getting the roof area for the computation of rainwater piping size, for two walls opposite of differing heights, add ____ of wall area above top of lower wall to the roof area.

    50%

  • 48

    For each 18.9 Lpm flow over 75.5 Lpm, the area of the sand interceptor inlet section is to be increased by _____.

    0.09 sqm

  • 49

    When the first compartment exceeds 3.7 m in length, an additional ____ shall be provided.

    manhole

  • 50

    What can be drained through an airbreak?

    air washer

  • YT1 Materials Engineer EXAM

    YT1 Materials Engineer EXAM

    ユーザ名非公開 · 100問 · 13日前

    YT1 Materials Engineer EXAM

    YT1 Materials Engineer EXAM

    100問 • 13日前
    ユーザ名非公開

    YT2 Materials Engineer EXAM

    YT2 Materials Engineer EXAM

    ユーザ名非公開 · 100問 · 13日前

    YT2 Materials Engineer EXAM

    YT2 Materials Engineer EXAM

    100問 • 13日前
    ユーザ名非公開

    Project Engineer YT 1

    Project Engineer YT 1

    ユーザ名非公開 · 100問 · 13日前

    Project Engineer YT 1

    Project Engineer YT 1

    100問 • 13日前
    ユーザ名非公開

    Project Engineer EXAM

    Project Engineer EXAM

    ユーザ名非公開 · 62問 · 13日前

    Project Engineer EXAM

    Project Engineer EXAM

    62問 • 13日前
    ユーザ名非公開

    Project Engineer EXAM 68

    Project Engineer EXAM 68

    ユーザ名非公開 · 100問 · 13日前

    Project Engineer EXAM 68

    Project Engineer EXAM 68

    100問 • 13日前
    ユーザ名非公開

    Project Engineer EXAM 82

    Project Engineer EXAM 82

    ユーザ名非公開 · 100問 · 13日前

    Project Engineer EXAM 82

    Project Engineer EXAM 82

    100問 • 13日前
    ユーザ名非公開

    July 2023 PE Refresher

    July 2023 PE Refresher

    ユーザ名非公開 · 70問 · 13日前

    July 2023 PE Refresher

    July 2023 PE Refresher

    70問 • 13日前
    ユーザ名非公開

    August 2019 Special PE Exam

    August 2019 Special PE Exam

    ユーザ名非公開 · 93問 · 13日前

    August 2019 Special PE Exam

    August 2019 Special PE Exam

    93問 • 13日前
    ユーザ名非公開

    RNPCP Chapter 1 to 5

    RNPCP Chapter 1 to 5

    ユーザ名非公開 · 86問 · 13日前

    RNPCP Chapter 1 to 5

    RNPCP Chapter 1 to 5

    86問 • 13日前
    ユーザ名非公開

    Plumbing Code 4

    Plumbing Code 4

    ユーザ名非公開 · 100問 · 13日前

    Plumbing Code 4

    Plumbing Code 4

    100問 • 13日前
    ユーザ名非公開

    Plumbing Code 5

    Plumbing Code 5

    ユーザ名非公開 · 100問 · 13日前

    Plumbing Code 5

    Plumbing Code 5

    100問 • 13日前
    ユーザ名非公開

    Plumbing Code 6

    Plumbing Code 6

    ユーザ名非公開 · 100問 · 13日前

    Plumbing Code 6

    Plumbing Code 6

    100問 • 13日前
    ユーザ名非公開

    Plumbing Code 7

    Plumbing Code 7

    ユーザ名非公開 · 100問 · 13日前

    Plumbing Code 7

    Plumbing Code 7

    100問 • 13日前
    ユーザ名非公開

    Plumbing Code 8

    Plumbing Code 8

    ユーザ名非公開 · 100問 · 13日前

    Plumbing Code 8

    Plumbing Code 8

    100問 • 13日前
    ユーザ名非公開

    Plumbing Code 3

    Plumbing Code 3

    ユーザ名非公開 · 100問 · 13日前

    Plumbing Code 3

    Plumbing Code 3

    100問 • 13日前
    ユーザ名非公開

    Sanitation, Plumbing Design, and Installation 2

    Sanitation, Plumbing Design, and Installation 2

    ユーザ名非公開 · 97問 · 13日前

    Sanitation, Plumbing Design, and Installation 2

    Sanitation, Plumbing Design, and Installation 2

    97問 • 13日前
    ユーザ名非公開

    Sanitation, Plumbing Design, and Installation 1

    Sanitation, Plumbing Design, and Installation 1

    ユーザ名非公開 · 99問 · 13日前

    Sanitation, Plumbing Design, and Installation 1

    Sanitation, Plumbing Design, and Installation 1

    99問 • 13日前
    ユーザ名非公開

    Sanitation, Plumbing Design, and Installation 3

    Sanitation, Plumbing Design, and Installation 3

    ユーザ名非公開 · 96問 · 13日前

    Sanitation, Plumbing Design, and Installation 3

    Sanitation, Plumbing Design, and Installation 3

    96問 • 13日前
    ユーザ名非公開

    Sanitation, Plumbing Design, and Installation 4

    Sanitation, Plumbing Design, and Installation 4

    ユーザ名非公開 · 95問 · 13日前

    Sanitation, Plumbing Design, and Installation 4

    Sanitation, Plumbing Design, and Installation 4

    95問 • 13日前
    ユーザ名非公開

    Sanitation, Plumbing Design, and Installation 5

    Sanitation, Plumbing Design, and Installation 5

    ユーザ名非公開 · 97問 · 13日前

    Sanitation, Plumbing Design, and Installation 5

    Sanitation, Plumbing Design, and Installation 5

    97問 • 13日前
    ユーザ名非公開

    問題一覧

  • 1

    This type of ground surface generate more rainwater runoff

    concrete sidewalk

  • 2

    What is the minimum condensate pipe diameter of a cooling equipment with capacity through 125 ToR?

    38 mm

  • 3

    The principal artery of the venting system to which vent branches are connected.

    Main Vent

  • 4

    The side walls of a Septic Tank shall be at least ____ above the liquid depth.

    9"

  • 5

    The extension of a soil or waste stack above the highest horizontal drain connected to the stack.

    Stack Vent

  • 6

    Maximum horizontal distance of the trap arm with a diameter of 38 mm

    1.07 m

  • 7

    What is the estimated sewage flow rate of bowling alleys with snack bar only?

    283.9 LpD per lane

  • 8

    Minimum water seal of a grease trap

    51 mm

  • 9

    Wet venting is limited to _____ fixtures

    4

  • 10

    Prohibited vent pipe material below ground

    Galvanized wrought iron

  • 11

    A water that stands in or passes through the ground

    Ground water

  • 12

    All condensers and sumps shall be properly trapped at the outlet with a deep seal trap extending to within ____ of the bottom of the tank.

    6"

  • 13

    Maximum length of a tailpiece

    0.6 m

  • 14

    What is the maximum length allowed for a vent stack serving 48 DFU?

    55

  • 15

    Which among the choices is a prohibited trap?

    Crown trap

  • 16

    A group vent pipe that connects to the vent stack

    circuit vent

  • 17

    The minimum depth of the sand interceptor under the invert of the outlet pipe is _____.

    610 mm

  • 18

    What is the minimum distance from disposal field to another disposal field?

    1.2 m

  • 19

    In a granule test of a water closet, the initial flush of three different flushes must result in no more than _____ on average remaining in the bowl.

    125

  • 20

    The size of a vent pipe is determined by _____.

    FU and length

  • 21

    Determine the size of horizontal rainwater piping with a slope of 2% for a 350 sqm roof in an area where the the rainfall is 102 mm/hr.

    127 mm

  • 22

    Maximum number of slip joint fitting that may be used on the outlet side of a trap

    1

  • 23

    Elastomeric gasketed and rubber-ring joints shall comply with _____ installation standard

    IAPMO

  • 24

    Water closets that are made to accommodate overweight and obese people

    Bariatric Water Closet

  • 25

    Normally in Manila, the rainfall intensity used is _____.

    102 mm

  • 26

    The maximum trap loading of a pipe size 76 mm

    6

  • 27

    Minimum dimension of a sand interceptor's inlet opening

    0.2 sqm

  • 28

    If the development is mostly built of concrete flooring, how can this affect the stormwater sizing?

    the drains might be larger

  • 29

    If a septic tank can have an effective capacity of 4000 L, how much does the secondary compartment hold?

    1,333 L

  • 30

    _____ are recommended for oil handling piping works

    Neoprene gaskets

  • 31

    When disposal fields and/or seepage pits are installed in sloping ground, the minimum horizontal distance between any part of the leaching system and ground surface shall be _____.

    15 feet

  • 32

    What is the storage factor for self-service auto washers?

    1.5

  • 33

    What is the gauge pressure to be maintained for air tests as substitute for water test in water pipings?

    344.5 kpa

  • 34

    Minimum spacing between trenches or leaching beds

    1.20 m

  • 35

    What is the sewage that turns dark and smell unpleasantly due to anaerobic decomposition?

    septic

  • 36

    What is required when a soil or waste stack extends 10 or more stories?

    Parallel vent stack

  • 37

    What downspout size would you specify for a 800 sqm roof with a rainfall intensity around the area of 152.4 mm/hr?

    152 mm

  • 38

    What will be the size of 0.5% sloped circular bottom gutter serving a roof area of 180 sqm, and the rainfall intensity around the area is 76 mm/hr?

    178 mm

  • 39

    What is an underground drain pipe that receives only subsurface or seepage water and convey it to a sump for disposal by gravity flow or by lift pump?

    subsoil drain

  • 40

    What is the horizontal distance required of a vent pipe from any openable window, door opening, air intake, or vent shaft?

    3 m

  • 41

    Connects directly with an individual trap underneath or behind the fixture

    Backvent Pipe

  • 42

    Vertical vent pipes installed in a roof used for other purposes shall extend a minimum of _____ above such roof.

    2.1 m

  • 43

    Every abandoned building sewer shall be plugged or capped within _____ of the property line

    1.5 m

  • 44

    Rainwater piping located within a medium height building basement area shall be of Galvanized Iron, _____.

    Schedule 30

  • 45

    Minimum distance of a 32 mm trap arm diameter to a vent

    64 mm

  • 46

    Which of the following may be true about the sovent system?

    it has lesser maintenance cost

  • 47

    In getting the roof area for the computation of rainwater piping size, for two walls opposite of differing heights, add ____ of wall area above top of lower wall to the roof area.

    50%

  • 48

    For each 18.9 Lpm flow over 75.5 Lpm, the area of the sand interceptor inlet section is to be increased by _____.

    0.09 sqm

  • 49

    When the first compartment exceeds 3.7 m in length, an additional ____ shall be provided.

    manhole

  • 50

    What can be drained through an airbreak?

    air washer