  • 1

    Premises wiring shall not be electrically connected to a supply system unless the latter contains, for any grounded conductor of the interior system, a corresponding conductor that is grounded.

    Connection to Grounded System

  • 2

    An insulated conductor that is intended for use as a grounded conductor, where contained within a flexible cord, shall be identified by a white or gray outer finish

    Flexible Cords

  • 3

    All devices, excluding panelboards, provided with terminals for the attachment of conductors and intended for connection to more than one side of the circuit

    Device Terminals

  • 4

    No grounded conductor shall be attached to any terminal or lead so as to reverse the designated polarity

    Polarity of Connections

  • 5

    Branch circuits recognized by this article shall be rated in accordance with the maximum permitted ampere rating or setting of the overcurrent device

    Rating

  • 6

    Multiwire branch circuits shall supply only _____________

    Line-to-Neutral Loads

  • 7

    In dwelling units and guest rooms or guest suites of hotels, motels, and similar occupancies, the voltage shall not exceed 230 volts

    Occupancy Limitation

  • 8

    Where connected to a branch circuit having a rating in excess of 20 amperes, __________ shall be of the heavy-duty type. A heavy-duty lampholder shall have a rating of not less than 660 watts if of the admedium type, or not less than 750 watts if of any other type.

    Lampholders

  • 9

    A cord connector that is supplied by a permanently connected ____________ shall be considered a receptacle outlet.

    Cord Pendants

  • 10

    A receptacle outlet shall be installed wherever flexible cords with attachment plugs are used. Where flexible cords are permitted to be permanently connected, receptacles shall be permitted to be omitted for such cords.

    Cord Connections

  • 11

    Appliance receptacle outlets installed in a dwelling unit for specific appliances, such as laundry equipment, shall be installed within 1 800 mm of the intended location of the appliance.

    Appliance Outlets

  • 12

    In dwelling units, at least one receptacle outlet shall be installed in __________ within 900 mm

    Bathrooms

  • 13

    For a one-family dwelling and each unit of a two- family dwelling that is at grade level, at least one receptacle outlet accessible at grade level and not more than 2 000 mm above grade

    Outdoor Outlets

  • 14

    An outlet supplying luminaire(s) [lighting fixture(s)] shall be calculated based on the maximum volt-ampere rating of the equipment and lamps for which the luminaire(s) [fixture(s)] is rated.

    Luminaires (Lighting Fixtures)

  • 15

    Outlets for heavy-duty lampholders shall be calculated at a minimum of 600 volt-amperes.

    Heavy-Duty Lampholders

  • 16

    Sign and outline lighting outlets shall be calculated at a minimum of 1200 volt-amperes for each required branch circuit

    Sign and Outline Lighting

  • 17

    suitable for use underground; other raceways round in cross section, listed for underground use, and embedded in earth or concrete.

    Electrical Duct

  • 18

    heat transfer capability through a substance by conduction. It is the reciprocal of thermal conductivity and is designated Rho and expressed in the units °C-cm/watt.

    Thermal Resistivity

  • 19

    For raceways containing conductors of 22 mm2 or larger, and for cables containing conductors of 22 mm2 or larger

    Minimum Size

  • 20

    In pull boxes or junction boxes having any dimension over 1 800 mm

    Conductors in Pull or Junction Boxes

  • 21

    A fabricated assembly of insulated conductors in a flexible metallic enclosure.

    Armored Cable, Type AC

  • 22

    An assembly of parallel conductors formed integrally with an insulating material web specifically designed for field installation in surface metal raceway.

    Flat Cable Assembly, Type FC

  • 23

    A protective layer that is installed between the floor and Type FCC flat conductor cable to protect the cable from physical damage and may or may not be incorporated as an integral part of the cable.

    Bottom Shield

  • 24

    A connector designed to join Type FCC cables without using a junction box.

    Cable Connector

  • 25

    A complete wiring system for branch circuits that is designed for installation under carpet squares.

    FCC System

  • 26

    A single or multiconductor solid dielectric insulated cable rated 2 001 volts or higher.

    Medium Voltage Cable, Type MV

  • 27

    A factory assembly of one or more insulated circuit conductors with or without optical fiber members enclosed in an armor of interlocking metal tape, or a smooth orcorrugated metallic sheath. 3.30

    Metal Clad Cable, Type MC

  • 28

    The ___________ shall be of copper, aluminum, or copper-clad aluminum, solid or stranded. The minimum conductor size shall be 18 AWG copper and 3.5 mm2 (2.0 mm dia.) aluminum or copper-clad aluminum.

    Conductors

  • 29

    Insulated conductors enclosed within an overall nonmetallic jacket.

    Type NM

  • 30

    Insulated conductors enclosed within an overall, corrosion resistant, nonmetallic jacket.

    Type NMC

  • 31

    Insulated power or control conductors with signaling, data, and communications conductors within an overall nonmetallic jacket.

    Type NMS

  • 32

    A factory assembly of two or more insulated conductors, with or without associated bare or covered grounding conductors, under a nonmetallic jacket.

    Power and Control Tray Cable, Type TC

  • 33

    A threadable raceway of circular cross section designed for the physical protection and routing of conductors and cables and for use as an equipment grounding conductor when installed

    Rigid Metal Conduit (RMC)

  • 34

    A raceway of circular cross section made of helically wound, formed, interlocked metal strip.

    Flexible Metal Conduit (FMC)

  • 35

    A raceway of circular cross section having an outer liquidtight, nonmetallic,sunlight-resistant jacket over an inner flexible metal core with associated couplings, connectors, and fittings for the installation of electric conductors

    Liquidtight Flexible Metal Conduit (LFMC)

  • 36

    A raceway of circular cross section of various type

    Liquidtight Flexible Nonmetallic Conduit (LFNC)

  • 37

    An unthreaded thinwall raceway of circular cross section designed for the physical protection

    Electrical Metallic Tubing (EMT)

  • 38

    A raceway that is circular in cross section, flexible, metallic, and liquidtight without a nonmetallic jacket.

    Flexible Metallic Tubing (FMT)

  • 39

    A nonmetallic pliable corrugated raceway of circular cross section with integral or associated couplings, connectors, and fittings for the installation of electric conductors.

    Electrical Nonmetallic Tubing (ENT)

  • 40

    Flame retardant, nonmetallic enclosures with removable covers for housing and protecting electric wires, cable, and busbars in which conductors are laid in place after the wireway has been installed as a complete system.

    Nonmetallic Auxiliary Gutters

  • 41

    A nonmetallic pliable corrugated raceway of circular cross section with integral or associated couplings, connectors, and fittings for the installation of electric conductors.

    Electrical Nonmetallic Tubing (ENT)

  • 42

    A grounded metal enclosure containing factory- mounted, bare or insulated conductors, which are usually copper or aluminum bars, rods, or tubes.

    Busway

  • 43

    An assembly of insulated conductors with fittings and conductor terminations in a completely enclosed, ventilated protective metal housing. Cablebus is ordinarily assembled at the point of installation from the components furnished

    Cablebus

  • 44

    A single enclosed tubular space in a cellular metal floor member, the axis of the cell being parallel to the axis of the metal floor member.

    Cell

  • 45

    A transverse raceway for electric conductors, providing access to predetermined cells of a cellular metal floor, thereby permitting the installation of electric conductors from a distribution center to the cells.

    Header

  • 46

    Sheet metal troughs with hinged or removable covers for housing and protecting electric wires and cable and in which conductors are laid in place after the wireway has been installed as a complete system.

    Metal Wireways

  • 47

    Loads not exceeding the ampere and voltage ratings of the switch. Where particular load characteristics or limitations are specified as a condition of the listing, those restrictions

    Inductive Loads

  • 48

    A manufactured assembly designed to support and energize luminaires (lighting fixtures) that are capable of being readily repositioned on the track.

    Lighting Track

  • 49

    A length of pipe including pumps, valves, flanges, control devices, strainers, and/or similar equipment for conveying fluids.

    Pipeline

  • 50

    An electrical device that converts single-phase power to 3-phase electrical power.

    Phase Converter

  • 51

    A device that consists of a rotary transformer and capacitor panel(s) that permits the operation of 3- phase loads from a single-phase supply.

    Rotary-Phase Converter

  • 52

    A device without rotating parts, sized for a given 3- phase load to permit operation from a single-phase supply.

    Static-Phase Converter

  • 53

    The voltage calculated on the basis of 2 volts per cell for the lead-acid type and 1.2 volts per cell for the alkali type.

    Nominal Battery Voltage

  • 54

    A ____________________ is one that has no provision for the addition of water or electrolyte or for external measurement of electrolyte specific gravity.

    Sealed Cell or Battery

  • 55

    A battery comprised of one or more rechargeable cells of the lead-acid, nickel-cadmium, or other rechargeable electrochemical types.

    Storage Battery

  • AC2 - LM2 (Reviewer)

    AC2 - LM2 (Reviewer)

    ユーザ名非公開 · 38問 · 2年前

    AC2 - LM2 (Reviewer)

    AC2 - LM2 (Reviewer)

    38問 • 2年前
    ユーザ名非公開

    AC2 - SLM3 (Reviewer)

    AC2 - SLM3 (Reviewer)

    ユーザ名非公開 · 49問 · 2年前

    AC2 - SLM3 (Reviewer)

    AC2 - SLM3 (Reviewer)

    49問 • 2年前
    ユーザ名非公開

    HIRAC

    HIRAC

    ユーザ名非公開 · 35問 · 2年前

    HIRAC

    HIRAC

    35問 • 2年前
    ユーザ名非公開

    MSE Reviewer

    MSE Reviewer

    ユーザ名非公開 · 41問 · 2年前

    MSE Reviewer

    MSE Reviewer

    41問 • 2年前
    ユーザ名非公開

    EE12 Quiz 1

    EE12 Quiz 1

    ユーザ名非公開 · 41問 · 2年前

    EE12 Quiz 1

    EE12 Quiz 1

    41問 • 2年前
    ユーザ名非公開

    PEC Definition - Quiz 1

    PEC Definition - Quiz 1

    ユーザ名非公開 · 45問 · 2年前

    PEC Definition - Quiz 1

    PEC Definition - Quiz 1

    45問 • 2年前
    ユーザ名非公開

    PEC Quiz 2

    PEC Quiz 2

    ユーザ名非公開 · 30問 · 2年前

    PEC Quiz 2

    PEC Quiz 2

    30問 • 2年前
    ユーザ名非公開

    Chapter 5

    Chapter 5

    ユーザ名非公開 · 52問 · 2年前

    Chapter 5

    Chapter 5

    52問 • 2年前
    ユーザ名非公開

    Chapter 6

    Chapter 6

    ユーザ名非公開 · 33問 · 2年前

    Chapter 6

    Chapter 6

    33問 • 2年前
    ユーザ名非公開

    Quiz

    Quiz

    ユーザ名非公開 · 53問 · 2年前

    Quiz

    Quiz

    53問 • 2年前
    ユーザ名非公開

    Finals

    Finals

    ユーザ名非公開 · 57問 · 2年前

    Finals

    Finals

    57問 • 2年前
    ユーザ名非公開

    Fluids Finals

    Fluids Finals

    ユーザ名非公開 · 68問 · 2年前

    Fluids Finals

    Fluids Finals

    68問 • 2年前
    ユーザ名非公開

    問題一覧

  • 1

    Premises wiring shall not be electrically connected to a supply system unless the latter contains, for any grounded conductor of the interior system, a corresponding conductor that is grounded.

    Connection to Grounded System

  • 2

    An insulated conductor that is intended for use as a grounded conductor, where contained within a flexible cord, shall be identified by a white or gray outer finish

    Flexible Cords

  • 3

    All devices, excluding panelboards, provided with terminals for the attachment of conductors and intended for connection to more than one side of the circuit

    Device Terminals

  • 4

    No grounded conductor shall be attached to any terminal or lead so as to reverse the designated polarity

    Polarity of Connections

  • 5

    Branch circuits recognized by this article shall be rated in accordance with the maximum permitted ampere rating or setting of the overcurrent device

    Rating

  • 6

    Multiwire branch circuits shall supply only _____________

    Line-to-Neutral Loads

  • 7

    In dwelling units and guest rooms or guest suites of hotels, motels, and similar occupancies, the voltage shall not exceed 230 volts

    Occupancy Limitation

  • 8

    Where connected to a branch circuit having a rating in excess of 20 amperes, __________ shall be of the heavy-duty type. A heavy-duty lampholder shall have a rating of not less than 660 watts if of the admedium type, or not less than 750 watts if of any other type.

    Lampholders

  • 9

    A cord connector that is supplied by a permanently connected ____________ shall be considered a receptacle outlet.

    Cord Pendants

  • 10

    A receptacle outlet shall be installed wherever flexible cords with attachment plugs are used. Where flexible cords are permitted to be permanently connected, receptacles shall be permitted to be omitted for such cords.

    Cord Connections

  • 11

    Appliance receptacle outlets installed in a dwelling unit for specific appliances, such as laundry equipment, shall be installed within 1 800 mm of the intended location of the appliance.

    Appliance Outlets

  • 12

    In dwelling units, at least one receptacle outlet shall be installed in __________ within 900 mm

    Bathrooms

  • 13

    For a one-family dwelling and each unit of a two- family dwelling that is at grade level, at least one receptacle outlet accessible at grade level and not more than 2 000 mm above grade

    Outdoor Outlets

  • 14

    An outlet supplying luminaire(s) [lighting fixture(s)] shall be calculated based on the maximum volt-ampere rating of the equipment and lamps for which the luminaire(s) [fixture(s)] is rated.

    Luminaires (Lighting Fixtures)

  • 15

    Outlets for heavy-duty lampholders shall be calculated at a minimum of 600 volt-amperes.

    Heavy-Duty Lampholders

  • 16

    Sign and outline lighting outlets shall be calculated at a minimum of 1200 volt-amperes for each required branch circuit

    Sign and Outline Lighting

  • 17

    suitable for use underground; other raceways round in cross section, listed for underground use, and embedded in earth or concrete.

    Electrical Duct

  • 18

    heat transfer capability through a substance by conduction. It is the reciprocal of thermal conductivity and is designated Rho and expressed in the units °C-cm/watt.

    Thermal Resistivity

  • 19

    For raceways containing conductors of 22 mm2 or larger, and for cables containing conductors of 22 mm2 or larger

    Minimum Size

  • 20

    In pull boxes or junction boxes having any dimension over 1 800 mm

    Conductors in Pull or Junction Boxes

  • 21

    A fabricated assembly of insulated conductors in a flexible metallic enclosure.

    Armored Cable, Type AC

  • 22

    An assembly of parallel conductors formed integrally with an insulating material web specifically designed for field installation in surface metal raceway.

    Flat Cable Assembly, Type FC

  • 23

    A protective layer that is installed between the floor and Type FCC flat conductor cable to protect the cable from physical damage and may or may not be incorporated as an integral part of the cable.

    Bottom Shield

  • 24

    A connector designed to join Type FCC cables without using a junction box.

    Cable Connector

  • 25

    A complete wiring system for branch circuits that is designed for installation under carpet squares.

    FCC System

  • 26

    A single or multiconductor solid dielectric insulated cable rated 2 001 volts or higher.

    Medium Voltage Cable, Type MV

  • 27

    A factory assembly of one or more insulated circuit conductors with or without optical fiber members enclosed in an armor of interlocking metal tape, or a smooth orcorrugated metallic sheath. 3.30

    Metal Clad Cable, Type MC

  • 28

    The ___________ shall be of copper, aluminum, or copper-clad aluminum, solid or stranded. The minimum conductor size shall be 18 AWG copper and 3.5 mm2 (2.0 mm dia.) aluminum or copper-clad aluminum.

    Conductors

  • 29

    Insulated conductors enclosed within an overall nonmetallic jacket.

    Type NM

  • 30

    Insulated conductors enclosed within an overall, corrosion resistant, nonmetallic jacket.

    Type NMC

  • 31

    Insulated power or control conductors with signaling, data, and communications conductors within an overall nonmetallic jacket.

    Type NMS

  • 32

    A factory assembly of two or more insulated conductors, with or without associated bare or covered grounding conductors, under a nonmetallic jacket.

    Power and Control Tray Cable, Type TC

  • 33

    A threadable raceway of circular cross section designed for the physical protection and routing of conductors and cables and for use as an equipment grounding conductor when installed

    Rigid Metal Conduit (RMC)

  • 34

    A raceway of circular cross section made of helically wound, formed, interlocked metal strip.

    Flexible Metal Conduit (FMC)

  • 35

    A raceway of circular cross section having an outer liquidtight, nonmetallic,sunlight-resistant jacket over an inner flexible metal core with associated couplings, connectors, and fittings for the installation of electric conductors

    Liquidtight Flexible Metal Conduit (LFMC)

  • 36

    A raceway of circular cross section of various type

    Liquidtight Flexible Nonmetallic Conduit (LFNC)

  • 37

    An unthreaded thinwall raceway of circular cross section designed for the physical protection

    Electrical Metallic Tubing (EMT)

  • 38

    A raceway that is circular in cross section, flexible, metallic, and liquidtight without a nonmetallic jacket.

    Flexible Metallic Tubing (FMT)

  • 39

    A nonmetallic pliable corrugated raceway of circular cross section with integral or associated couplings, connectors, and fittings for the installation of electric conductors.

    Electrical Nonmetallic Tubing (ENT)

  • 40

    Flame retardant, nonmetallic enclosures with removable covers for housing and protecting electric wires, cable, and busbars in which conductors are laid in place after the wireway has been installed as a complete system.

    Nonmetallic Auxiliary Gutters

  • 41

    A nonmetallic pliable corrugated raceway of circular cross section with integral or associated couplings, connectors, and fittings for the installation of electric conductors.

    Electrical Nonmetallic Tubing (ENT)

  • 42

    A grounded metal enclosure containing factory- mounted, bare or insulated conductors, which are usually copper or aluminum bars, rods, or tubes.

    Busway

  • 43

    An assembly of insulated conductors with fittings and conductor terminations in a completely enclosed, ventilated protective metal housing. Cablebus is ordinarily assembled at the point of installation from the components furnished

    Cablebus

  • 44

    A single enclosed tubular space in a cellular metal floor member, the axis of the cell being parallel to the axis of the metal floor member.

    Cell

  • 45

    A transverse raceway for electric conductors, providing access to predetermined cells of a cellular metal floor, thereby permitting the installation of electric conductors from a distribution center to the cells.

    Header

  • 46

    Sheet metal troughs with hinged or removable covers for housing and protecting electric wires and cable and in which conductors are laid in place after the wireway has been installed as a complete system.

    Metal Wireways

  • 47

    Loads not exceeding the ampere and voltage ratings of the switch. Where particular load characteristics or limitations are specified as a condition of the listing, those restrictions

    Inductive Loads

  • 48

    A manufactured assembly designed to support and energize luminaires (lighting fixtures) that are capable of being readily repositioned on the track.

    Lighting Track

  • 49

    A length of pipe including pumps, valves, flanges, control devices, strainers, and/or similar equipment for conveying fluids.

    Pipeline

  • 50

    An electrical device that converts single-phase power to 3-phase electrical power.

    Phase Converter

  • 51

    A device that consists of a rotary transformer and capacitor panel(s) that permits the operation of 3- phase loads from a single-phase supply.

    Rotary-Phase Converter

  • 52

    A device without rotating parts, sized for a given 3- phase load to permit operation from a single-phase supply.

    Static-Phase Converter

  • 53

    The voltage calculated on the basis of 2 volts per cell for the lead-acid type and 1.2 volts per cell for the alkali type.

    Nominal Battery Voltage

  • 54

    A ____________________ is one that has no provision for the addition of water or electrolyte or for external measurement of electrolyte specific gravity.

    Sealed Cell or Battery

  • 55

    A battery comprised of one or more rechargeable cells of the lead-acid, nickel-cadmium, or other rechargeable electrochemical types.

    Storage Battery