  • 1

    Utilizes fluorescent lamps, high intensity discharge lamps, or neon tubing.

    Electric-Discharge Lighting

  • 2

    Electric-discharge tubing manufactured into shapes that form letters, parts of letters, skeleton tubing, outline lighting, other decorative elements, or art forms, and filled with various inert gases.

    Neon Tubing

  • 3

    Neon tubing that is itself the sign/outlines lighting and not attached to an enclosure.

    Skeleton Tubing

  • 4

    Incandescent and Fluorescent Lamps shall be rated not to exceed

    20 Amperes

  • 5

    Neon Lamps shall be rated not to exceed

    30 amperes

  • 6

    Flexible Metal Conduit - Shall be permitted as a bonding means in lengths not exceeding

    30 m

  • 7

    The parts not exceeding 50 mm in any dimension, not likely to be energized and spaced at least 19 mm from neon tubing shall not require bonding.

    Small Metal Parts

  • 8

    Shall be installed separate and remote, spaced at least 40 mm from the system for 100 Hz or less or 45 mm for systems 100 Hz and over.

    Nonmetallic Conduit

  • 9

    Shall be made of copper and not smaller than 2.0 mm? (1.6 mm dia.).

    Bonding Conductors

  • 10

    Shall have all metal parts and equipment grounding conductors bonded.

    Signs in Fountains

  • 11

    shall be a sheet copper or aluminum at least 0.50 mm thick. Using of sheet steel for the enclosure shall be at least 0.40 mm thick.

    Enclosure

  • 12

    Shall be an integral part of the attachment plug or shall be located in the power-supply cord within 300 mm.

    Ground-Fault Circuit Interrupter

  • 13

    The runway contact conductors shall be guarded, and bridge contact conductors shall be located or guarded in a manner that person cannot inadvertently touch energized current carrying parts.

    Locating or Guarding Contact Conductors

  • 14

    The extreme limit of displacement of the wire is within less than 40 mm

    Contact Wires

  • 15

    Shall have a minimum of 750 mm to access to live parts where the controls are enclosed in cabinets, the door(s) shall either open at least 90 degrees or be removable.

    Clearance

  • 16

    A lighting fixture intended for installation in the wall of a pool or fountain in a niche that is sealed against the entry of pool water.

    Dry-Niche Luminaire (Lighting Fixture)

  • 17

    A lighting fixture intended for installation in a forming shell mounted in a pool or fountain structure where the fixture will be completely surrounded by water.

    Wet-Niche Luminaire (Lighting Fixture)

  • 18

    A complete, environmentally protected unit consisting of solar cells, optics, inverter, and other components, exclusive of tracker, designed to generate ac power when exposed to sunlight.

    Alternating-Current Photovoltaic Module

  • 19

    A mechanically integrated assembly of modules or panels with a support structure and foundation, tracker, and other components, as required, to form a direct-current power-producing unit.

    Array

  • 20

    A photovoltaic array that has two outputs, each having opposite polarity to a common reference point or center tap.

    Bipolar Photovoltaic Array

  • 21

    A diode used to block reverse flow of current into a photovoltaic source circuit.

    Blocking Diode

  • 22

    Photovoltaic cells, devices, modules, or modular materials that are integrated into the outer surface/structure of a building and serve as the outer protective surface of that building.

    Building Integrated Photovoltaics

  • 23

    Equipment that controls the voltage or de current, or both, used to charge a battery

    Charge Controller

  • 24

    Equipment that regulates the charging process of a battery by diverting power from energy storage to DC or AC loads or to an interconnected utility service.

    Diversion Charge Controller

  • 25

    A system comprised of multiple power sources.

    Hybrid System

  • 26

    A solar photovoltaic system that operates in parallel with or may deliver power to an electrical production and distribution network.

    Interactive System

  • 27

    Equipment that is used to change voltage level or waveform, or both, of electrical energy [also known as a power conditioning unit (PCU) or power conversion system (PCS)] is a device that changes de input to an ac output. Inverters may also function as battery chargers that use alternating current from another source and convert it into direct current for charging batteries.

    Inverter

  • 28

    A complete, environmentally protected unit consisting of solar cells, optics, and other components, exclusive of tracker, designed to generate de power when exposed to sunlight.

    Module

  • 29

    A collection of modules mechanically fastened together, wired, and designed to provide a field-installable unit.

    Panel

  • 30

    The basic photovoltaic device that generates electricity when exposed to light

    Solar Cell

  • 31

    The total components and subsystems that, in combination, convert solar energy into electrical energy suitable for connection to utilization load.

    Solar Photovoltaic System

  • 32

    A solar photovoltaic system that supplies power independently of an electrical production and distribution network.

    Stand-Alone System

  • 33

    Roof-mounted de photovoltaic arrays located on dwellings shall be provided with the__________ to reduce fire hazards.

    Ground-Fault Protection

  • AC2 - LM2 (Reviewer)

    AC2 - LM2 (Reviewer)

    ユーザ名非公開 · 38問 · 2年前

    AC2 - LM2 (Reviewer)

    AC2 - LM2 (Reviewer)

    38問 • 2年前
    ユーザ名非公開

    AC2 - SLM3 (Reviewer)

    AC2 - SLM3 (Reviewer)

    ユーザ名非公開 · 49問 · 2年前

    AC2 - SLM3 (Reviewer)

    AC2 - SLM3 (Reviewer)

    49問 • 2年前
    ユーザ名非公開

    HIRAC

    HIRAC

    ユーザ名非公開 · 35問 · 2年前

    HIRAC

    HIRAC

    35問 • 2年前
    ユーザ名非公開

    MSE Reviewer

    MSE Reviewer

    ユーザ名非公開 · 41問 · 2年前

    MSE Reviewer

    MSE Reviewer

    41問 • 2年前
    ユーザ名非公開

    EE12 Quiz 1

    EE12 Quiz 1

    ユーザ名非公開 · 41問 · 2年前

    EE12 Quiz 1

    EE12 Quiz 1

    41問 • 2年前
    ユーザ名非公開

    PEC Definition - Quiz 1

    PEC Definition - Quiz 1

    ユーザ名非公開 · 45問 · 2年前

    PEC Definition - Quiz 1

    PEC Definition - Quiz 1

    45問 • 2年前
    ユーザ名非公開

    Quiz 2

    Quiz 2

    ユーザ名非公開 · 55問 · 2年前

    Quiz 2

    Quiz 2

    55問 • 2年前
    ユーザ名非公開

    PEC Quiz 2

    PEC Quiz 2

    ユーザ名非公開 · 30問 · 2年前

    PEC Quiz 2

    PEC Quiz 2

    30問 • 2年前
    ユーザ名非公開

    Chapter 5

    Chapter 5

    ユーザ名非公開 · 52問 · 2年前

    Chapter 5

    Chapter 5

    52問 • 2年前
    ユーザ名非公開

    Quiz

    Quiz

    ユーザ名非公開 · 53問 · 2年前

    Quiz

    Quiz

    53問 • 2年前
    ユーザ名非公開

    Finals

    Finals

    ユーザ名非公開 · 57問 · 2年前

    Finals

    Finals

    57問 • 2年前
    ユーザ名非公開

    Fluids Finals

    Fluids Finals

    ユーザ名非公開 · 68問 · 2年前

    Fluids Finals

    Fluids Finals

    68問 • 2年前
    ユーザ名非公開

    問題一覧

  • 1

    Utilizes fluorescent lamps, high intensity discharge lamps, or neon tubing.

    Electric-Discharge Lighting

  • 2

    Electric-discharge tubing manufactured into shapes that form letters, parts of letters, skeleton tubing, outline lighting, other decorative elements, or art forms, and filled with various inert gases.

    Neon Tubing

  • 3

    Neon tubing that is itself the sign/outlines lighting and not attached to an enclosure.

    Skeleton Tubing

  • 4

    Incandescent and Fluorescent Lamps shall be rated not to exceed

    20 Amperes

  • 5

    Neon Lamps shall be rated not to exceed

    30 amperes

  • 6

    Flexible Metal Conduit - Shall be permitted as a bonding means in lengths not exceeding

    30 m

  • 7

    The parts not exceeding 50 mm in any dimension, not likely to be energized and spaced at least 19 mm from neon tubing shall not require bonding.

    Small Metal Parts

  • 8

    Shall be installed separate and remote, spaced at least 40 mm from the system for 100 Hz or less or 45 mm for systems 100 Hz and over.

    Nonmetallic Conduit

  • 9

    Shall be made of copper and not smaller than 2.0 mm? (1.6 mm dia.).

    Bonding Conductors

  • 10

    Shall have all metal parts and equipment grounding conductors bonded.

    Signs in Fountains

  • 11

    shall be a sheet copper or aluminum at least 0.50 mm thick. Using of sheet steel for the enclosure shall be at least 0.40 mm thick.

    Enclosure

  • 12

    Shall be an integral part of the attachment plug or shall be located in the power-supply cord within 300 mm.

    Ground-Fault Circuit Interrupter

  • 13

    The runway contact conductors shall be guarded, and bridge contact conductors shall be located or guarded in a manner that person cannot inadvertently touch energized current carrying parts.

    Locating or Guarding Contact Conductors

  • 14

    The extreme limit of displacement of the wire is within less than 40 mm

    Contact Wires

  • 15

    Shall have a minimum of 750 mm to access to live parts where the controls are enclosed in cabinets, the door(s) shall either open at least 90 degrees or be removable.

    Clearance

  • 16

    A lighting fixture intended for installation in the wall of a pool or fountain in a niche that is sealed against the entry of pool water.

    Dry-Niche Luminaire (Lighting Fixture)

  • 17

    A lighting fixture intended for installation in a forming shell mounted in a pool or fountain structure where the fixture will be completely surrounded by water.

    Wet-Niche Luminaire (Lighting Fixture)

  • 18

    A complete, environmentally protected unit consisting of solar cells, optics, inverter, and other components, exclusive of tracker, designed to generate ac power when exposed to sunlight.

    Alternating-Current Photovoltaic Module

  • 19

    A mechanically integrated assembly of modules or panels with a support structure and foundation, tracker, and other components, as required, to form a direct-current power-producing unit.

    Array

  • 20

    A photovoltaic array that has two outputs, each having opposite polarity to a common reference point or center tap.

    Bipolar Photovoltaic Array

  • 21

    A diode used to block reverse flow of current into a photovoltaic source circuit.

    Blocking Diode

  • 22

    Photovoltaic cells, devices, modules, or modular materials that are integrated into the outer surface/structure of a building and serve as the outer protective surface of that building.

    Building Integrated Photovoltaics

  • 23

    Equipment that controls the voltage or de current, or both, used to charge a battery

    Charge Controller

  • 24

    Equipment that regulates the charging process of a battery by diverting power from energy storage to DC or AC loads or to an interconnected utility service.

    Diversion Charge Controller

  • 25

    A system comprised of multiple power sources.

    Hybrid System

  • 26

    A solar photovoltaic system that operates in parallel with or may deliver power to an electrical production and distribution network.

    Interactive System

  • 27

    Equipment that is used to change voltage level or waveform, or both, of electrical energy [also known as a power conditioning unit (PCU) or power conversion system (PCS)] is a device that changes de input to an ac output. Inverters may also function as battery chargers that use alternating current from another source and convert it into direct current for charging batteries.

    Inverter

  • 28

    A complete, environmentally protected unit consisting of solar cells, optics, and other components, exclusive of tracker, designed to generate de power when exposed to sunlight.

    Module

  • 29

    A collection of modules mechanically fastened together, wired, and designed to provide a field-installable unit.

    Panel

  • 30

    The basic photovoltaic device that generates electricity when exposed to light

    Solar Cell

  • 31

    The total components and subsystems that, in combination, convert solar energy into electrical energy suitable for connection to utilization load.

    Solar Photovoltaic System

  • 32

    A solar photovoltaic system that supplies power independently of an electrical production and distribution network.

    Stand-Alone System

  • 33

    Roof-mounted de photovoltaic arrays located on dwellings shall be provided with the__________ to reduce fire hazards.

    Ground-Fault Protection