    the minimum inlet and outlet size for sand interceptor

    76 mm

  • 2

    Minimum distance of a 32 mm trap arm diameter to a vent

    64 mm

  • 3

    The side walls of a Septic Tank shall be at least ____ above the liquid depth.

    9"

  • 4

    If a septic tank can have an effective capacity of 4000 L, how much does the secondary compartment hold?

    1,333 L

  • 5

    A 203 mm diameter and larger sewer may have a slope of _____.

    0.5%

  • 6

    Vertical vent pipes installed in a roof used for other purposes shall extend a minimum of _____ above such roof.

    2.1 m

  • 7

    Wet venting is limited to _____ fixtures

    4

  • 8

    What is the sewage that turns dark and smell unpleasantly due to anaerobic decomposition?

    septic

  • 9

    When the first compartment exceeds 3.7 m in length, an additional ____ shall be provided.

    manhole

  • 10

    Minimum spacing between trenches or leaching beds

    1.20 m

  • 11

    What is the gauge pressure to be maintained for air tests as substitute for water test in water pipings?

    344.5 kpa

  • 12

    In getting the roof area for the computation of rainwater piping size, for two walls opposite of differing heights, add ____ of wall area above top of lower wall to the roof area.

    50%

  • 13

    _____ are recommended for oil handling piping works.

    Neoprene gaskets

  • 14

    All condensers and sumps shall be properly trapped at the outlet with a deep seal trap extending to within ____ of the bottom of the tank.

    6"

  • 15

    Elastomeric gasketed and rubber-ring joints shall comply with _____ installation standard

    IAPMO

  • 16

    What is the maximum length allowed for a vent stack serving 48 DFU?

    55

  • 17

    Normally in Manila, the rainfall intensity used is _____.

    102 mm

  • 18

    The bottom of the water pipe, at all points shall be at least _____ above the top of the sewer or drain line.

    0.3 m

  • 19

    What will be the size of 0.5% sloped circular bottom gutter serving a roof area of 180 sqm, and the rainfall intensity around the area is 76 mm/hr?

    178 mm

  • 20

    What can be drained through an airbreak?

    air washer

  • 21

    Which among the choices is a prohibited trap?

    Crown trap

  • 22

    Determine the size of horizontal rainwater piping with a slope of 2% for a 350 sqm roof in an area where the the rainfall is 102 mm/hr.

    127 mm

  • 23

    The principal artery of the venting system to which vent branches are connected.

    Main Vent

  • 24

    What is the estimated sewage flow rate of bowling alleys with snack bar only?

    238.9 LpD per lane

  • 25

    Maximum number of slip joint fitting that may be used on the outlet side of a trap

    1

  • 26

    A group vent pipe that connects to the vent stack

    circuit vent

  • 27

    A water that stands in or passes through the ground

    Ground water

  • 28

    What is an underground drain pipe that receives only sub-surface or seepage water and convey it to a sump for disposal by gravity flow or by lift pump?

    subsoil drain

  • 29

    Rainwater piping located within a medium height building basement area shall be of Galvanized Iron, _____.

    Schedule 30

  • 30

    What is the storage factor for self-service auto washers?

    1.5

  • 31

    Water closets that are made to accommodate overweight and obese people

    Bariatric Water Closet

  • 32

    What downspout size would you specify for a 800 sqm roof with a rainfall intensity around the area of 152.4 mm/hr?

    152 mm

  • 33

    The maximum trap loading of a pipe size 76 mm

    6

  • 34

    Septic tanks should be cleaned when scum or sludge occupies ____ of the tank volume.

    1/3

  • 35

    What is required when a soil or waste stack extends 10 or more stories?

    Parallel vent stack

  • 36

    Prohibited vent pipe material below ground

    Galvanized wrought iron

  • 37

    Maximum length of a tailpiece

    0.6 m

  • 38

    Every abandoned building sewer shall be plugged or capped within _____ of the property line.

    1.5 m

  • 39

    What is the minimum condensate pipe diameter of a cooling equipment with capacity through 125 ToR?

    38 mm

  • 40

    Horizontal distance of the trap arm with a diameter of 38 mm

    1.07 m

  • 41

    What is the horizontal distance required of a vent pipe from any openable window, door opening, air intake, or vent shaft?

    3 m

  • 42

    The size of a vent pipe is determined by _____.

    FU and length

  • 43

    For accessible toilets, signs on walls and doors should be located at a maximum height of _____.

    1.60 m

  • 44

    In a granule test of a water closet, the initial flush of three different flushes must result in no more than _____ on average remaining in the bowl.

    125

  • 45

    Minimum dimension of a sand interceptor's inlet opening

    0.2 sqm

  • 46

    The minimum depth of the sand interceptor under the invert of the outlet pipe is _____.

    610 mm

  • 47

    What is the minimum distance from disposal field to another disposal field?

    1.2 m

  • 48

    Minimum water seal of a grease trap

    51 mm

  • 49

    ointing method for soft copper water tubing

    Flared Joint

  • 50

    Connects directly with an individual trap underneath or behind the fixture

    Backvent Pipe

  • Littons part 2-0314

    Littons part 2-0314

    Ian Calasang · 60問 · 2年前

    Littons part 2-0314

    Littons part 2-0314

    60問 • 2年前
    Ian Calasang

    PSAD TERMS 2011-2018

    PSAD TERMS 2011-2018

    Ian Calasang · 3回閲覧 · 60問 · 2年前

    PSAD TERMS 2011-2018

    PSAD TERMS 2011-2018

    3回閲覧 • 60問 • 2年前
    Ian Calasang

    Littons

    Littons

    Ian Calasang · 4回閲覧 · 61問 · 2年前

    Littons

    Littons

    4回閲覧 • 61問 • 2年前
    Ian Calasang

    Probability

    Probability

    Ian Calasang · 61問 · 3年前

    Probability

    Probability

    61問 • 3年前
    Ian Calasang

    DPWH II

    DPWH II

    Ian Calasang · 43問 · 3年前

    DPWH II

    DPWH II

    43問 • 3年前
    Ian Calasang

    MSTHC Terms

    MSTHC Terms

    Ian Calasang · 53問 · 3年前

    MSTHC Terms

    MSTHC Terms

    53問 • 3年前
    Ian Calasang

    PSAD TERMS 2011-2018

    PSAD TERMS 2011-2018

    Ian Calasang · 54問 · 2年前

    PSAD TERMS 2011-2018

    PSAD TERMS 2011-2018

    54問 • 2年前
    Ian Calasang

    LOOKSFAM MODULES GILLE updated[josh t.]

    LOOKSFAM MODULES GILLE updated[josh t.]

    Ian Calasang · 37問 · 3年前

    LOOKSFAM MODULES GILLE updated[josh t.]

    LOOKSFAM MODULES GILLE updated[josh t.]

    37問 • 3年前
    Ian Calasang

    HGE TERMS CE REF 4

    HGE TERMS CE REF 4

    Ian Calasang · 36問 · 2年前

    HGE TERMS CE REF 4

    HGE TERMS CE REF 4

    36問 • 2年前
    Ian Calasang

    Engineering Economics

    Engineering Economics

    Ian Calasang · 94問 · 3年前

    Engineering Economics

    Engineering Economics

    94問 • 3年前
    Ian Calasang

    dpwh

    dpwh

    Ian Calasang · 34問 · 3年前

    dpwh

    dpwh

    34問 • 3年前
    Ian Calasang

    Terms-1

    Terms-1

    Ian Calasang · 89問 · 2年前

    Terms-1

    Terms-1

    89問 • 2年前
    Ian Calasang

    Terms-2

    Terms-2

    Ian Calasang · 89問 · 2年前

    Terms-2

    Terms-2

    89問 • 2年前
    Ian Calasang

    Terms-3

    Terms-3

    Ian Calasang · 90問 · 2年前

    Terms-3

    Terms-3

    90問 • 2年前
    Ian Calasang

    Plumb. Code -1

    Plumb. Code -1

    Ian Calasang · 50問 · 2年前

    Plumb. Code -1

    Plumb. Code -1

    50問 • 2年前
    Ian Calasang

    Plumb. Code - 2

    Plumb. Code - 2

    Ian Calasang · 50問 · 2年前

    Plumb. Code - 2

    Plumb. Code - 2

    50問 • 2年前
    Ian Calasang

    SPDI-1

    SPDI-1

    Ian Calasang · 50問 · 2年前

    SPDI-1

    SPDI-1

    50問 • 2年前
    Ian Calasang

    SPDI-2

    SPDI-2

    Ian Calasang · 47問 · 2年前

    SPDI-2

    SPDI-2

    47問 • 2年前
    Ian Calasang

    everything numbers! Test 5

    everything numbers! Test 5

    Ian Calasang · 80問 · 2年前

    everything numbers! Test 5

    everything numbers! Test 5

    80問 • 2年前
    Ian Calasang

    Codes/Laws -7

    Codes/Laws -7

    Ian Calasang · 60問 · 2年前

    Codes/Laws -7

    Codes/Laws -7

    60問 • 2年前
    Ian Calasang

    midterm fle

    midterm fle

    Ian Calasang · 6問 · 1年前

    midterm fle

    midterm fle

    6問 • 1年前
    Ian Calasang

    問題一覧

  • 1

    the minimum inlet and outlet size for sand interceptor

    76 mm

  • 2

    Minimum distance of a 32 mm trap arm diameter to a vent

    64 mm

  • 3

    The side walls of a Septic Tank shall be at least ____ above the liquid depth.

    9"

  • 4

    If a septic tank can have an effective capacity of 4000 L, how much does the secondary compartment hold?

    1,333 L

  • 5

    A 203 mm diameter and larger sewer may have a slope of _____.

    0.5%

  • 6

    Vertical vent pipes installed in a roof used for other purposes shall extend a minimum of _____ above such roof.

    2.1 m

  • 7

    Wet venting is limited to _____ fixtures

    4

  • 8

    What is the sewage that turns dark and smell unpleasantly due to anaerobic decomposition?

    septic

  • 9

    When the first compartment exceeds 3.7 m in length, an additional ____ shall be provided.

    manhole

  • 10

    Minimum spacing between trenches or leaching beds

    1.20 m

  • 11

    What is the gauge pressure to be maintained for air tests as substitute for water test in water pipings?

    344.5 kpa

  • 12

    In getting the roof area for the computation of rainwater piping size, for two walls opposite of differing heights, add ____ of wall area above top of lower wall to the roof area.

    50%

  • 13

    _____ are recommended for oil handling piping works.

    Neoprene gaskets

  • 14

    All condensers and sumps shall be properly trapped at the outlet with a deep seal trap extending to within ____ of the bottom of the tank.

    6"

  • 15

    Elastomeric gasketed and rubber-ring joints shall comply with _____ installation standard

    IAPMO

  • 16

    What is the maximum length allowed for a vent stack serving 48 DFU?

    55

  • 17

    Normally in Manila, the rainfall intensity used is _____.

    102 mm

  • 18

    The bottom of the water pipe, at all points shall be at least _____ above the top of the sewer or drain line.

    0.3 m

  • 19

    What will be the size of 0.5% sloped circular bottom gutter serving a roof area of 180 sqm, and the rainfall intensity around the area is 76 mm/hr?

    178 mm

  • 20

    What can be drained through an airbreak?

    air washer

  • 21

    Which among the choices is a prohibited trap?

    Crown trap

  • 22

    Determine the size of horizontal rainwater piping with a slope of 2% for a 350 sqm roof in an area where the the rainfall is 102 mm/hr.

    127 mm

  • 23

    The principal artery of the venting system to which vent branches are connected.

    Main Vent

  • 24

    What is the estimated sewage flow rate of bowling alleys with snack bar only?

    238.9 LpD per lane

  • 25

    Maximum number of slip joint fitting that may be used on the outlet side of a trap

    1

  • 26

    A group vent pipe that connects to the vent stack

    circuit vent

  • 27

    A water that stands in or passes through the ground

    Ground water

  • 28

    What is an underground drain pipe that receives only sub-surface or seepage water and convey it to a sump for disposal by gravity flow or by lift pump?

    subsoil drain

  • 29

    Rainwater piping located within a medium height building basement area shall be of Galvanized Iron, _____.

    Schedule 30

  • 30

    What is the storage factor for self-service auto washers?

    1.5

  • 31

    Water closets that are made to accommodate overweight and obese people

    Bariatric Water Closet

  • 32

    What downspout size would you specify for a 800 sqm roof with a rainfall intensity around the area of 152.4 mm/hr?

    152 mm

  • 33

    The maximum trap loading of a pipe size 76 mm

    6

  • 34

    Septic tanks should be cleaned when scum or sludge occupies ____ of the tank volume.

    1/3

  • 35

    What is required when a soil or waste stack extends 10 or more stories?

    Parallel vent stack

  • 36

    Prohibited vent pipe material below ground

    Galvanized wrought iron

  • 37

    Maximum length of a tailpiece

    0.6 m

  • 38

    Every abandoned building sewer shall be plugged or capped within _____ of the property line.

    1.5 m

  • 39

    What is the minimum condensate pipe diameter of a cooling equipment with capacity through 125 ToR?

    38 mm

  • 40

    Horizontal distance of the trap arm with a diameter of 38 mm

    1.07 m

  • 41

    What is the horizontal distance required of a vent pipe from any openable window, door opening, air intake, or vent shaft?

    3 m

  • 42

    The size of a vent pipe is determined by _____.

    FU and length

  • 43

    For accessible toilets, signs on walls and doors should be located at a maximum height of _____.

    1.60 m

  • 44

    In a granule test of a water closet, the initial flush of three different flushes must result in no more than _____ on average remaining in the bowl.

    125

  • 45

    Minimum dimension of a sand interceptor's inlet opening

    0.2 sqm

  • 46

    The minimum depth of the sand interceptor under the invert of the outlet pipe is _____.

    610 mm

  • 47

    What is the minimum distance from disposal field to another disposal field?

    1.2 m

  • 48

    Minimum water seal of a grease trap

    51 mm

  • 49

    ointing method for soft copper water tubing

    Flared Joint

  • 50

    Connects directly with an individual trap underneath or behind the fixture

    Backvent Pipe