ログイン

EEE2 QUIZ

EEE2 QUIZ
30問 • 2年前
  • PJ ZERO
  • 通報

    問題一覧

  • 1

    is defined as the changes in terminal voltage expressed as a fraction of full load rated voltage when the load at a given power factor is removed while keeping the speed and field current constant

    Voltage Regulation

  • 2

    the difference between the sending end and the receiving end voltages a line.

    Voltage Drop

  • 3

    the nominal value assigned to a line or apparatus or a system of a given voltage class

    Nominal Voltage

  • 4

    the voltage at which performance and operating characteristics of the apparatus are referred.

    Rated Voltage

  • 5

    the voltage measured at the end of the service entrance apparatus

    Service Voltage

  • 6

    the voltage measured at the end of the apparatus

    Utilization Voltage

  • 7

    The reference Voltage

    Base Voltage

  • 8

    The performance of distribution systems and quality of the service provided are measured in terms of freedom from interruptions and maintenance of satisfactory levels at the costumer’s premise that is within the limits appropriate for this type of service.

    Voltage Quality and Standards

  • 9

    Automatic Voltage Regulation is always provided by:

    Bus regulation at the Sub-Station. Individual Feeder Regulation in the substation. supplementary regulation along the main regulators mounted on poles

  • 10

    Feeders should not exceed the following

    Above 33kV (-) 12.5% to (+)10% Up to 33kV Low Voltage

  • 11

    are used to protect equipment, machinery , components and devices, in electrical and electronic circuit, against short circuit, over current and earth fault

    Protective Devices

  • 12

    It protects the current from overcurrent through its metal strip which is to liquefy the current when the flow is high.

    Fuse

  • 13

    being more reliable and accurate and with the ability to detect other type of faults than overloads and overcurrent that can occur in networks and equipment

    Protective Relays

  • 14

    The protective relay should operate positively and isolate the faulty portion of the power system as and when required. A reliable relaying system must be dependable and secure.

    Reliability

  • 15

    Protection is arranged in zone, which should cover the power system completely, having no part unprotected

    Selectivity

  • 16

    This term, applied to protection on distinct from power network, refers to the ability of the system to remain inert to all load conditions and fault external to the relevant zone.

    Stability

  • 17

    The function of automatic protection is to isolate fault from the power system in a very much shorter time than could be isolated manually, even with great deal of supervision

    Speed

  • 18

    a term frequently used when referring to the minimum operating limit of a complete protective system.

    Sensitivity

  • 19

    Protective devices are selected and assigned to protect a specific part of the power system.

    Zones of Protection

  • 20

    The overlapping of zones allows a protective device to provide backup protection to the adjacent zone, also referred to as the backup or overreached zone.

    Primary and Backup Protection

  • 21

    permanently connected through a charger to the station AC service, and normally, during steady-state conditions, it floats on the charger.

    Battery

  • 22

    Commonly known as the Instrument Transformer, current and potential transformer.

    Transducer

  • 23

    A relay needs information from the system to make a decision.

    Input

  • 24

    Many protection relays have adjustable __________. The user programs settings (pick-up levels) that allow the relay to make a decision

    Settings

  • 25

    Once the inputs are connected and the settings are programmed, the relay compares these values and makes a decision.

    Processes

  • 26

    The relay has several ways of communicating that a decision has been made.

    Output

  • 27

    function as to detect the fault and also to initiate the appropriate control signal such as the tripping signal

    Protective Relays

  • 28

    Relays this is a programmable relay whose the function is to initiate a sequence of actions leading to the automatic reclosing of the circuit breaker.

    Reclosing and Synchronizing

  • 29

    Monitor power supplies (voltage, current, power, phase), temperatures, and other analogue signals and detects abnormalities in machines and equipment by determining values against alarm thresholds

    Monitoring Relays

  • 30

    these relays which assist other relays by applying supplementary actions

    Auxiliary Relays

  • EE14 MIDTERM REVIEWER

    EE14 MIDTERM REVIEWER

    PJ ZERO · 42問 · 2年前

    EE14 MIDTERM REVIEWER

    EE14 MIDTERM REVIEWER

    42問 • 2年前
    PJ ZERO

    EE14 MIDTERM REVIEWER

    EE14 MIDTERM REVIEWER

    PJ ZERO · 42問 · 2年前

    EE14 MIDTERM REVIEWER

    EE14 MIDTERM REVIEWER

    42問 • 2年前
    PJ ZERO

    FME9 MIDTERM EXAM

    FME9 MIDTERM EXAM

    PJ ZERO · 25問 · 2年前

    FME9 MIDTERM EXAM

    FME9 MIDTERM EXAM

    25問 • 2年前
    PJ ZERO

    FME9 2

    FME9 2

    PJ ZERO · 22問 · 2年前

    FME9 2

    FME9 2

    22問 • 2年前
    PJ ZERO

    FLUIDS FINALS

    FLUIDS FINALS

    PJ ZERO · 24問 · 2年前

    FLUIDS FINALS

    FLUIDS FINALS

    24問 • 2年前
    PJ ZERO

    FLUIDS FINALS

    FLUIDS FINALS

    PJ ZERO · 24問 · 2年前

    FLUIDS FINALS

    FLUIDS FINALS

    24問 • 2年前
    PJ ZERO

    FLUIDS MIDTERM REVIEWER

    FLUIDS MIDTERM REVIEWER

    PJ ZERO · 13問 · 1年前

    FLUIDS MIDTERM REVIEWER

    FLUIDS MIDTERM REVIEWER

    13問 • 1年前
    PJ ZERO

    問題一覧

  • 1

    is defined as the changes in terminal voltage expressed as a fraction of full load rated voltage when the load at a given power factor is removed while keeping the speed and field current constant

    Voltage Regulation

  • 2

    the difference between the sending end and the receiving end voltages a line.

    Voltage Drop

  • 3

    the nominal value assigned to a line or apparatus or a system of a given voltage class

    Nominal Voltage

  • 4

    the voltage at which performance and operating characteristics of the apparatus are referred.

    Rated Voltage

  • 5

    the voltage measured at the end of the service entrance apparatus

    Service Voltage

  • 6

    the voltage measured at the end of the apparatus

    Utilization Voltage

  • 7

    The reference Voltage

    Base Voltage

  • 8

    The performance of distribution systems and quality of the service provided are measured in terms of freedom from interruptions and maintenance of satisfactory levels at the costumer’s premise that is within the limits appropriate for this type of service.

    Voltage Quality and Standards

  • 9

    Automatic Voltage Regulation is always provided by:

    Bus regulation at the Sub-Station. Individual Feeder Regulation in the substation. supplementary regulation along the main regulators mounted on poles

  • 10

    Feeders should not exceed the following

    Above 33kV (-) 12.5% to (+)10% Up to 33kV Low Voltage

  • 11

    are used to protect equipment, machinery , components and devices, in electrical and electronic circuit, against short circuit, over current and earth fault

    Protective Devices

  • 12

    It protects the current from overcurrent through its metal strip which is to liquefy the current when the flow is high.

    Fuse

  • 13

    being more reliable and accurate and with the ability to detect other type of faults than overloads and overcurrent that can occur in networks and equipment

    Protective Relays

  • 14

    The protective relay should operate positively and isolate the faulty portion of the power system as and when required. A reliable relaying system must be dependable and secure.

    Reliability

  • 15

    Protection is arranged in zone, which should cover the power system completely, having no part unprotected

    Selectivity

  • 16

    This term, applied to protection on distinct from power network, refers to the ability of the system to remain inert to all load conditions and fault external to the relevant zone.

    Stability

  • 17

    The function of automatic protection is to isolate fault from the power system in a very much shorter time than could be isolated manually, even with great deal of supervision

    Speed

  • 18

    a term frequently used when referring to the minimum operating limit of a complete protective system.

    Sensitivity

  • 19

    Protective devices are selected and assigned to protect a specific part of the power system.

    Zones of Protection

  • 20

    The overlapping of zones allows a protective device to provide backup protection to the adjacent zone, also referred to as the backup or overreached zone.

    Primary and Backup Protection

  • 21

    permanently connected through a charger to the station AC service, and normally, during steady-state conditions, it floats on the charger.

    Battery

  • 22

    Commonly known as the Instrument Transformer, current and potential transformer.

    Transducer

  • 23

    A relay needs information from the system to make a decision.

    Input

  • 24

    Many protection relays have adjustable __________. The user programs settings (pick-up levels) that allow the relay to make a decision

    Settings

  • 25

    Once the inputs are connected and the settings are programmed, the relay compares these values and makes a decision.

    Processes

  • 26

    The relay has several ways of communicating that a decision has been made.

    Output

  • 27

    function as to detect the fault and also to initiate the appropriate control signal such as the tripping signal

    Protective Relays

  • 28

    Relays this is a programmable relay whose the function is to initiate a sequence of actions leading to the automatic reclosing of the circuit breaker.

    Reclosing and Synchronizing

  • 29

    Monitor power supplies (voltage, current, power, phase), temperatures, and other analogue signals and detects abnormalities in machines and equipment by determining values against alarm thresholds

    Monitoring Relays

  • 30

    these relays which assist other relays by applying supplementary actions

    Auxiliary Relays