問題
is defined as the changes in terminal voltage expressed as a fraction of full load rated voltage when the load at a given power factor is removed while keeping the speed and field current constant
問題
the difference between the sending end and the receiving end voltages a line.
問題
the nominal value assigned to a line or apparatus or a system of a given voltage class
問題
the voltage at which performance and operating characteristics of the apparatus are referred.
問題
the voltage measured at the end of the service entrance apparatus
問題
the voltage measured at the end of the apparatus
問題
The reference Voltage
問題
The performance of distribution systems and quality of the service provided are measured in terms of freedom from interruptions and maintenance of satisfactory levels at the costumer’s premise that is within the limits appropriate for this type of service.
問題
Automatic Voltage Regulation is always provided by:
問題
Feeders should not exceed the following
EEE2 QUIZ
得点
0 / 10
正答率
0%
正解: 0
不正解: 0
未解答: 10
問題一覧
1
is defined as the changes in terminal voltage expressed as a fraction of full load rated voltage when the load at a given power factor is removed while keeping the speed and field current constantVoltage Regulation
2
the difference between the sending end and the receiving end voltages a line.Voltage Drop
3
the nominal value assigned to a line or apparatus or a system of a given voltage classNominal Voltage
4
the voltage at which performance and operating characteristics of the apparatus are referred.Rated Voltage
5
the voltage measured at the end of the service entrance apparatusService Voltage
6
the voltage measured at the end of the apparatusUtilization Voltage
7
The reference VoltageBase Voltage
8
The performance of distribution systems and quality of the service provided are measured in terms of freedom from interruptions and maintenance of satisfactory levels at the costumer’s premise that is within the limits appropriate for this type of service.Voltage Quality and Standards
9
Automatic Voltage Regulation is always provided by:Bus regulation at the Sub-Station. Individual Feeder Regulation in the substation. supplementary regulation along the main regulators mounted on poles
10
Feeders should not exceed the followingAbove 33kV (-) 12.5% to (+)10% Up to 33kV Low Voltage
11
are used to protect equipment, machinery , components and devices, in electrical and electronic circuit, against short circuit, over current and earth faultProtective Devices
12
It protects the current from overcurrent through its metal strip which is to liquefy the current when the flow is high.Fuse
13
being more reliable and accurate and with the ability to detect other type of faults than overloads and overcurrent that can occur in networks and equipmentProtective Relays
14
The protective relay should operate positively and isolate the faulty portion of the power system as and when required. A reliable relaying system must be dependable and secure.Reliability
15
Protection is arranged in zone, which should cover the power system completely, having no part unprotectedSelectivity
16
This term, applied to protection on distinct from power network, refers to the ability of the system to remain inert to all load conditions and fault external to the relevant zone.Stability
17
The function of automatic protection is to isolate fault from the power system in a very much shorter time than could be isolated manually, even with great deal of supervisionSpeed
18
a term frequently used when referring to the minimum operating limit of a complete protective system.Sensitivity
19
Protective devices are selected and assigned to protect a specific part of the power system.Zones of Protection
20
The overlapping of zones allows a protective device to provide backup protection to the adjacent zone, also referred to as the backup or overreached zone.Primary and Backup Protection
21
permanently connected through a charger to the station AC service, and normally, during steady-state conditions, it floats on the charger.Battery
22
Commonly known as the Instrument Transformer, current and potential transformer.Transducer
23
A relay needs information from the system to make a decision.Input
24
Many protection relays have adjustable __________. The user programs settings (pick-up levels) that allow the relay to make a decisionSettings
25
Once the inputs are connected and the settings are programmed, the relay compares these values and makes a decision.Processes
26
The relay has several ways of communicating that a decision has been made.Output
27
function as to detect the fault and also to initiate the appropriate control signal such as the tripping signalProtective Relays
28
Relays this is a programmable relay whose the function is to initiate a sequence of actions leading to the automatic reclosing of the circuit breaker.Reclosing and Synchronizing
29
Monitor power supplies (voltage, current, power, phase), temperatures, and other analogue signals and detects abnormalities in machines and equipment by determining values against alarm thresholdsMonitoring Relays
30
these relays which assist other relays by applying supplementary actionsAuxiliary Relays