Introduction to Substations
問題一覧
1
As the core heats the oil, the oil rises. The oil is then forced against the case of the transformer where it radiates heat into the atmosphere and cools. As it cools, the oil circulates down to the bottom of the core.
2
Electrical devices that monitor current flow within the substation for relaying and metering purposes
3
Electrical Devices used to create isolation points within a substation
4
Two winding transformers that step down high voltage to a low voltage that can be read by instruments for metering and relaying
5
Allows a circuit breaker to be removed from service for maintenance without disrupting power flow. The load is transferred to an adjacent circuit breaker by opening and closing a series of disconnects and energizing the transfer bus.
6
Located adjacent to the generating station and are designed to step the voltage up to transmission levels. Voltage change may be from 13.8 kV to 500kV
7
Provide voltage changes that remain at the transmission level. This voltage change may be from 500kV to 230kV
8
typically located near load centers. their main function is to change the voltage from a higher transmission voltage (ea 345kV) to a subtransmission voltage (ea 69kV). These subtransmission circuits the travel to the distribution substations.
9
usually located in the middle of the load centers and step voltage down from subtransmission levels to distribution levels (ea 138kV to 12kV)
10
-Changing the voltage of circuits from 1 level to another -Connecting or disconnecting lines or equipment from each other -Controlling the flow of power -Recording flow of power and related data
11
-Generation Substation -Transmission Substation -Subtransmission Substation -Distribution Substation
12
If one circuit fails or needs to be take out of service for maintenance, power is supplied to the station using the alternate circuit.
13
protects the transformer and distribution bus from fault conditions similar to a circuit breaker; however, typically not set to reclose, since most faults are permanent.
14
To ensure all ground connections are of the same potential
15
Key equipment such as relays, meters, and batteries. It may also contain communication hardware that allows some station equipment to be operated from a remote location
16
Before construction,maintenance, or operation is preformed
17
To allow the utility to confirm conditions of a station and record certain key data that indicates the operation of the system
18
-Protect electrical equipment and lines from abnormal conditions that occur -Isolate piece of equipment or line for maintenance
19
-Mechanical -Pneumatic and Mechanical -Hydraulic and Mechanical
20
-Single blade -Gang-Operated -Motor-Operated
21
The oil temperature, the sensoring point of the thermometer is physically located at the hottest spot usually at the center of secondary windings
22
Because the oil servers 2 purposes it insulates energized equipment and acts as a cooling agent. Impurities can drastically lower the dielectric strength of oil.
23
commonly used in power transformers as a blanket to help keep moisture from being absorbed by the oil. Space between the top of the oil level and the top of the power transformer case
24
the turns ratio is much greater than that of a regulator
25
Detect abnormal conditions on the power system and these initiate action to isolate or correct the conditions
26
-Programmable settings -Automatic self-check and diagnosis -Multiple relay functions such as over-current, over-voltage and under voltage -Telephone or radio interface, allowing remote programming and interrogation
27
Electromechanical relays have a target that drops (usually a red flag) to indicate that relay has operated.
28
-Not a type but a function, it opens up the power circuit breaker and operates under 2 conditions: Time over-current or Instantaneous over-current. -Time over-current tends to be a lower level of fault current; fault is somewhere down the line -Instantaneous over-current is a solid fault very high level and close to the source (usually in the 1st half of the circuit)
29
Batteries provide DC voltage used to operate power circuit breakers
30
•Three-Phase ammeter •VARS or wattmeter •Three overcurrent relays •Lockout relay
31
a panel located in the control house that will turn a light on to indicate some malfunction in the substation
Electrical Testing Equipment
Electrical Testing Equipment
Maxwell Nemir · 26問 · 1年前Electrical Testing Equipment
Electrical Testing Equipment
26問 • 1年前Electrical Systems
Electrical Systems
Maxwell Nemir · 25問 · 1年前Electrical Systems
Electrical Systems
25問 • 1年前Applied Mathematics
Applied Mathematics
Maxwell Nemir · 25問 · 1年前Applied Mathematics
Applied Mathematics
25問 • 1年前Into to power delivery
Into to power delivery
Maxwell Nemir · 23問 · 1年前Into to power delivery
Into to power delivery
23問 • 1年前Electronics
Electronics
Maxwell Nemir · 24問 · 1年前Electronics
Electronics
24問 • 1年前AC Fundmentals
AC Fundmentals
Maxwell Nemir · 25問 · 1年前AC Fundmentals
AC Fundmentals
25問 • 1年前Substation Safety 2
Substation Safety 2
Maxwell Nemir · 25問 · 1年前Substation Safety 2
Substation Safety 2
25問 • 1年前Rigging
Rigging
Maxwell Nemir · 11問 · 1年前Rigging
Rigging
11問 • 1年前Disconnects and Switches
Disconnects and Switches
Maxwell Nemir · 25問 · 1年前Disconnects and Switches
Disconnects and Switches
25問 • 1年前OSHA 2
OSHA 2
Maxwell Nemir · 25問 · 1年前OSHA 2
OSHA 2
25問 • 1年前White Hat Test
White Hat Test
Maxwell Nemir · 27問 · 1年前White Hat Test
White Hat Test
27問 • 1年前White hat test #2
White hat test #2
Maxwell Nemir · 18問 · 1年前White hat test #2
White hat test #2
18問 • 1年前Into to power delivery
Into to power delivery
Maxwell Nemir · 23問 · 7ヶ月前Into to power delivery
Into to power delivery
23問 • 7ヶ月前問題一覧
1
As the core heats the oil, the oil rises. The oil is then forced against the case of the transformer where it radiates heat into the atmosphere and cools. As it cools, the oil circulates down to the bottom of the core.
2
Electrical devices that monitor current flow within the substation for relaying and metering purposes
3
Electrical Devices used to create isolation points within a substation
4
Two winding transformers that step down high voltage to a low voltage that can be read by instruments for metering and relaying
5
Allows a circuit breaker to be removed from service for maintenance without disrupting power flow. The load is transferred to an adjacent circuit breaker by opening and closing a series of disconnects and energizing the transfer bus.
6
Located adjacent to the generating station and are designed to step the voltage up to transmission levels. Voltage change may be from 13.8 kV to 500kV
7
Provide voltage changes that remain at the transmission level. This voltage change may be from 500kV to 230kV
8
typically located near load centers. their main function is to change the voltage from a higher transmission voltage (ea 345kV) to a subtransmission voltage (ea 69kV). These subtransmission circuits the travel to the distribution substations.
9
usually located in the middle of the load centers and step voltage down from subtransmission levels to distribution levels (ea 138kV to 12kV)
10
-Changing the voltage of circuits from 1 level to another -Connecting or disconnecting lines or equipment from each other -Controlling the flow of power -Recording flow of power and related data
11
-Generation Substation -Transmission Substation -Subtransmission Substation -Distribution Substation
12
If one circuit fails or needs to be take out of service for maintenance, power is supplied to the station using the alternate circuit.
13
protects the transformer and distribution bus from fault conditions similar to a circuit breaker; however, typically not set to reclose, since most faults are permanent.
14
To ensure all ground connections are of the same potential
15
Key equipment such as relays, meters, and batteries. It may also contain communication hardware that allows some station equipment to be operated from a remote location
16
Before construction,maintenance, or operation is preformed
17
To allow the utility to confirm conditions of a station and record certain key data that indicates the operation of the system
18
-Protect electrical equipment and lines from abnormal conditions that occur -Isolate piece of equipment or line for maintenance
19
-Mechanical -Pneumatic and Mechanical -Hydraulic and Mechanical
20
-Single blade -Gang-Operated -Motor-Operated
21
The oil temperature, the sensoring point of the thermometer is physically located at the hottest spot usually at the center of secondary windings
22
Because the oil servers 2 purposes it insulates energized equipment and acts as a cooling agent. Impurities can drastically lower the dielectric strength of oil.
23
commonly used in power transformers as a blanket to help keep moisture from being absorbed by the oil. Space between the top of the oil level and the top of the power transformer case
24
the turns ratio is much greater than that of a regulator
25
Detect abnormal conditions on the power system and these initiate action to isolate or correct the conditions
26
-Programmable settings -Automatic self-check and diagnosis -Multiple relay functions such as over-current, over-voltage and under voltage -Telephone or radio interface, allowing remote programming and interrogation
27
Electromechanical relays have a target that drops (usually a red flag) to indicate that relay has operated.
28
-Not a type but a function, it opens up the power circuit breaker and operates under 2 conditions: Time over-current or Instantaneous over-current. -Time over-current tends to be a lower level of fault current; fault is somewhere down the line -Instantaneous over-current is a solid fault very high level and close to the source (usually in the 1st half of the circuit)
29
Batteries provide DC voltage used to operate power circuit breakers
30
•Three-Phase ammeter •VARS or wattmeter •Three overcurrent relays •Lockout relay
31
a panel located in the control house that will turn a light on to indicate some malfunction in the substation