Summary of Material Thickness and Weight
Summary of Material Thickness and Weight
ユーザ名非公開 · 19問 · 2年前Summary of Material Thickness and Weight
Summary of Material Thickness and Weight
19問 • 2年前ユーザ名非公開
Feb 2024 PB5
Feb 2024 PB5
ユーザ名非公開 · 7問 · 2年前Feb 2024 PB5
Feb 2024 PB5
7問 • 2年前ユーザ名非公開
Possible Questions
Possible Questions
ユーザ名非公開 · 6問 · 2年前Possible Questions
Possible Questions
6問 • 2年前ユーザ名非公開
Clamps and Hangers Figures
Clamps and Hangers Figures
ユーザ名非公開 · 18問 · 2年前Clamps and Hangers Figures
Clamps and Hangers Figures
18問 • 2年前ユーザ名非公開
Hammers
Hammers
ユーザ名非公開 · 7問 · 2年前Hammers
Hammers
7問 • 2年前ユーザ名非公開
Pliers
Pliers
ユーザ名非公開 · 22問 · 2年前Pliers
Pliers
22問 • 2年前ユーザ名非公開
問題一覧
1
It is commonly found in water. It multiplies where temperatures are between 20-45°C and nutrients are available. The bacteria are dormant below 20°C and do not survive above 60°C.
Legionella bacteria
2
A type of pipe fitting for a Yoke Vent.
1/8 bend
3
Length of house sewer from the inner face of the foundation wall of a building to the junction with another sewer.
4-5 ft
4
Minimum width of a septic tank.
0.90 m
5
Minimum length of a septic tank.
1.50 m
6
Minimum liquid depth for a septic tank.
0.60 m
7
Minimum size of trap and waste branch for a pedestal urínal.
3 in
8
Minimum size of trap or branch for a bidet.
38 mm
9
Diameter of drum trap
0.16 m
10
Minimum length of a drum trap
0.20 m
11
Maximum length of a drum trap
0.32 m
12
Maximum spacing of waste outlets of one trap that serve three single compartment sinks.
0.75 m
13
Maximum length of the tailpiece from any fixture.
0.60 m
14
Minimum diameter of pipe sleeve
25 mm
15
Minimum pipe sleeve for 64mm diameter uPVC pipe.
75 mm
16
Minimum diameter of an individual vent.
32 mm
17
Maximum distance of vent from trap seal.
1.5 m
18
Minimum extension of the VSTR above the roof.
150 mm
19
Minimum vertical extension of VSTR from any roof deck where it is protruded.
2.1 m
20
Minimum extension of VSTR above any other vertical
surface.
300 mm
21
Minimum height of a branch vent above the fixture it is venting.
150 mm
22
Minimum height of vent above the highest level rim
of the fixtures served before offsetting horizontally.
152 mm
23
Minimum distance of the VSTR from any openable window.
0.30 m
24
Minimum extension of the VSTR above an openable window.
0.90 m
25
Minimum distance of vent away from any lot line, alley and street boundary lines.
0.90 m
26
Minimum horizontal distance of any VSTR from a roof deck used for other purposes aside from protection from weather.
3 m