  • 1

    a solar heated system shall use a double walled heat exchanger which is exposed or double walled to the atmosphere between walls

    true

  • 2

    A pipe connecting upward from a soil or waste stack to a vent for the pupose of preventing pressure

    yoke vent

  • 3

    the minimum service pressure at the point of outlet discharge for all fixtures except direct flush valves shall be

    8 psi

  • 4

    this is a condition which develops on the interior of a pipe due to corrosive materials resulting in the creation of small lumps on the inner walls of the pipe

    tuberculation

  • 5

    the relief valve element must extend

    into the side or top within 6" from the top

  • 6

    the minimum size vent through any roof is

    3"

  • 7

    commercial dishwashing machines and similar dishwashing equipment using hot water for sanitizing shall be provided with a sufficient supply of hot water at

    180 degrees

  • 8

    pressure relive valves for hot water heaters shall be set to blow of at the maximum working pressure rating of the water heater but not to exceed

    150 psi or 210 degrees

  • 9

    drinking fountains or devices shall not be installed

    as an integral part of or connected to any other plumbing fixture

  • 10

    a double fire hose connection that runs from outside the building wall through a gate valve and a check valve to the fore stand pipe is called

    a siamese connection

  • 11

    the unobstructed vertical distance through the free atmosphere between the lowest opening from any pipe or faucet supplying potable water is called

    air gap

  • 12

    the activating handle of a flush valve in public restrooms shall be a minimum of ______________ above the flood rim of the bowl

    10"

  • 13

    floor drains shall be trapped and have a minimum water seal of

    2" to 4"

  • 14

    a residential dishwashing discharge

    May not empty into a food waste disposal unit

  • 15

    the vertical distance from the fixture outlet to the trap weir shall

    not exceed 24"

  • 16

    the minimum size clean out plug for 4" pipe is

    4"

  • 17

    a cleanout shall be provided at, or no more than_________feet above the base of each vertical waste or soil stack.

    4'

  • 18

    where commercial food waste grinders are utilized, the waste shall discharge

    directly into the building drainage system and not through an interceptor

  • 19

    a fixture unit drainage is the mathematical factor used by the plumbing industry as a means of estimating the probable load in the drainage system cause by discharge of various plumbing fixtures. note: laboratory test have shown that the rate of discharge of an ordinary lavatory with a normal 1 1/4" outlet trap, and waste is about___________ gallons per minute

    7.5

  • 20

    no piping shall be laid parallel to footings or outside bearing walls closer than

    18"

  • 21

    horizontal drainage piping of three inches in diameter shall be installed with a fall of not less than _____________ inch per foot

    1/4

  • 22

    each structure in which building drains are installed shall have one stack vent not less than _____________ inches in diameter carrried full size through the roof to the outside atmosphere for each building

    3"

  • 23

    where a roof is to be used for any purpose other than weather protection, the vent extension shall be run at least _________ above the roof

    7'

  • 24

    soil and waste stacks in buildings having more than ten branch intervals shall be provided with a ________ at each tenth interval installed, beginning with the top floor or may be installed midway between the first and twentieth interval

    relief vent

  • 25

    where potable water supply piping must cross a sewer line below grade, a vertical seperation of ______ is required

    18"

  • 26

    the minimum size supply line for a water closet with a flush valve shall be

    1"

  • 27

    no portion of the drainage system installed underground or below a basement or cellar shall be less than __________ inches in diameter

    2"

  • 28

    a combination waste and vent shall be permitted

    only where structural conditions preclude conventional plumbing

  • 29

    the minimum service pressure for a direct flush valve

    shall not be less than 15 psi

  • 30

    all vent and branch vent piping shall have a minimum grade of ________ and connected as to drain back to the soil oe waste pipe

    1/8 per foot

  • 31

    what is the D.F.U for a 2" fixture drain or trap?

    3

  • 32

    saddles to connect ice makers for refrigerators

    are prohibited

  • 33

    no steam pipe shall connect to any part of a drainage or plumbing system, nor shall any water ____________ degrees be discharged into any part of the drainage system

    above 180 degrees

  • 34

    when strict water main pressure exceeds 80 psi, what must be installed before the water service enters or ties into the building water distribution system

    a pressure reducing valve with a bypass and relief

  • 35

    the vertical distance between the crown weir and the top dip of the trap is called

    the trap seal

  • 36

    the maximum number of drainage fixtures units on a 4" horizontal branch drain installed at a 1/4" per foot slope is

    100 D.F.U s

  • 37

    plumbing systems are designed to prevent a pressure differential no greater than

    1" water column

  • 38

    where is the trap located on a bath water typ "P" trap is used

    directly below the tub "waste and overflow"

  • 39

    how many drainage fixture units may be put on a 2" horizontal drain?

    6

  • 40

    sumps receiving the discharge of more than ___________ water closets shall be prvided with duplex pumping equpment

    6

  • 41

    in a potable water supply tank, the water supply inlet to the tank shall have a minimum air gap of at least _______ inches

    6

  • 42

    the maximum developed length of a dead end in a water supply system allowed is

    2 feet

  • 43

    when backfilling a trench, until the crown of the pipe is covered by atleast _________ of tamped earth cre shall be excercised in backfilling trenches to ensure that the pipe beneath is secured

    18"

  • 44

    for a continous or semi-continous flow into a drainage system, such as from a pump, ejector, or similar devices, ___________ fixtures units(s) shall be considered to be equal to each gallon per minute of flow

    2

  • 45

    this type of venting only applies to floor drains and floor outlet fixtures which depend on siphonage for proper operation

    circuit vent

  • 46

    a device used to protect the quality of water, fail safe in design, securing the potable water system by isolating a heat exchanger when the pressure between the potable water and the heat exchange medium drops below a preset level is called

    pressure gradiant monitor

  • 47

    vent connecting to the drain pipe through a fitting at an angle not greater than 45 degrees to the vertical is called

    side vent

  • 48

    sanitary waste, gray water or mixtures containing harmful substances including but not limited to ethylene, glycol, hydrocarbons, oils, ammonia refrigerants, and hydrazine is called

    toxic transfer fluid

  • 49

    what is the maximum number of water closet allowed on a three inch horizontal waste pipe

    2

  • 50

    adding a backflow device to a water supply system creates a/an

    closed system