1
the unobstructed vertical distance through the free atmosphere between the lowest opening from any pipe or faucet supplying potable water is called
air gap
2
pressure relive valves for hot water heaters shall be set to blow of at the maximum working pressure rating of the water heater but not to exceed
150 psi or 210 degrees
3
this is a condition which develops on the interior of a pipe due to corrosive materials resulting in the creation of small lumps on the inner walls of the pipe
tuberculation
4
a device used to protect the quality of water, fail safe in design, securing the potable water system by isolating a heat exchanger when the pressure between the potable water and the heat exchange medium drops below a preset level is called
pressure gradiant monitor
5
a combination waste and vent shall be permitted
only where structural conditions preclude conventional plumbing
6
the maximum number of drainage fixtures units on a 4" horizontal branch drain installed at a 1/4" per foot slope is
100 D.F.U s
7
the vertical distance between the crown weir and the top dip of the trap is called
the trap seal
8
in a potable water supply tank, the water supply inlet to the tank shall have a minimum air gap of at least _______ inches
6
9
the minimum size vent through any roof is
3"
10
the relief valve element must extend
into the side or top within 6" from the top
11
all vent and branch vent piping shall have a minimum grade of ________ and connected as to drain back to the soil oe waste pipe
1/8 per foot
12
a double fire hose connection that runs from outside the building wall through a gate valve and a check valve to the fore stand pipe is called
a siamese connection
13
the minimum size clean out plug for 4" pipe is
4"
14
each structure in which building drains are installed shall have one stack vent not less than _____________ inches in diameter carrried full size through the roof to the outside atmosphere for each building
3"
15
plumbing systems are designed to prevent a pressure differential no greater than
1" water column
16
how many drainage fixture units may be put on a 2" horizontal drain?
6
17
adding a backflow device to a water supply system creates a/an
closed system
18
what is the D.F.U for a 2" fixture drain or trap?
3
19
no piping shall be laid parallel to footings or outside bearing walls closer than
18"
20
where potable water supply piping must cross a sewer line below grade, a vertical seperation of ______ is required
18"
21
commercial dishwashing machines and similar dishwashing equipment using hot water for sanitizing shall be provided with a sufficient supply of hot water at
180 degrees
22
the activating handle of a flush valve in public restrooms shall be a minimum of ______________ above the flood rim of the bowl
10"
23
A pipe connecting upward from a soil or waste stack to a vent for the pupose of preventing pressure
yoke vent
24
what is the maximum number of water closet allowed on a three inch horizontal waste pipe
2
25
sumps receiving the discharge of more than ___________ water closets shall be prvided with duplex pumping equpment
6
26
where a roof is to be used for any purpose other than weather protection, the vent extension shall be run at least _________ above the roof
7'
27
where is the trap located on a bath water typ "P" trap is used
directly below the tub "waste and overflow"
28
the vertical distance from the fixture outlet to the trap weir shall
not exceed 24"
29
a residential dishwashing discharge
May not empty into a food waste disposal unit
30
when backfilling a trench, until the crown of the pipe is covered by atleast _________ of tamped earth cre shall be excercised in backfilling trenches to ensure that the pipe beneath is secured
18"
31
no portion of the drainage system installed underground or below a basement or cellar shall be less than __________ inches in diameter
2"
32
the minimum service pressure for a direct flush valve
shall not be less than 15 psi
33
no steam pipe shall connect to any part of a drainage or plumbing system, nor shall any water ____________ degrees be discharged into any part of the drainage system
above 180 degrees
34
soil and waste stacks in buildings having more than ten branch intervals shall be provided with a ________ at each tenth interval installed, beginning with the top floor or may be installed midway between the first and twentieth interval
relief vent
35
vent connecting to the drain pipe through a fitting at an angle not greater than 45 degrees to the vertical is called
side vent
36
the minimum service pressure at the point of outlet discharge for all fixtures except direct flush valves shall be
8 psi
37
saddles to connect ice makers for refrigerators
are prohibited
38
floor drains shall be trapped and have a minimum water seal of
2" to 4"
39
where commercial food waste grinders are utilized, the waste shall discharge
directly into the building drainage system and not through an interceptor
40
a solar heated system shall use a double walled heat exchanger which is exposed or double walled to the atmosphere between walls
true
41
for a continous or semi-continous flow into a drainage system, such as from a pump, ejector, or similar devices, ___________ fixtures units(s) shall be considered to be equal to each gallon per minute of flow
2
42
the minimum size supply line for a water closet with a flush valve shall be
1"
43
sanitary waste, gray water or mixtures containing harmful substances including but not limited to ethylene, glycol, hydrocarbons, oils, ammonia refrigerants, and hydrazine is called
toxic transfer fluid
44
this type of venting only applies to floor drains and floor outlet fixtures which depend on siphonage for proper operation
circuit vent
45
when strict water main pressure exceeds 80 psi, what must be installed before the water service enters or ties into the building water distribution system
a pressure reducing valve with a bypass and relief
46
horizontal drainage piping of three inches in diameter shall be installed with a fall of not less than _____________ inch per foot
1/4
47
the maximum developed length of a dead end in a water supply system allowed is
2 feet
48
a cleanout shall be provided at, or no more than_________feet above the base of each vertical waste or soil stack.
4'
49
a fixture unit drainage is the mathematical factor used by the plumbing industry as a means of estimating the probable load in the drainage system cause by discharge of various plumbing fixtures. note: laboratory test have shown that the rate of discharge of an ordinary lavatory with a normal 1 1/4" outlet trap, and waste is about___________ gallons per minute
7.5
50
drinking fountains or devices shall not be installed
as an integral part of or connected to any other plumbing fixture