1
All pressure relief valves shall be inspected
weekly
2
According to Table 8.1.2 Summary of Fire Pumps Inspection, Testing and Maintenance, Diesel Engine Exhaust systems, the condensate drain trap is what type of inspection?
CHECK
3
During the weekly inspection of the pump assembly, the controller selector switch should be in the _____ position.
auto
4
Any abnormality observed during inspection or testing shall be reported promptly to the ______________________ for correcting the abnormality.
PERSON RESPONSIBLE
5
Test results and evaluation: The interpretation of the test Results shall be the basis of determination of the __________ of the pump assembly.
PERFORMANCE
6
The purpose of testing the pump assembly is to _________________ operation upon demand and continuous delivery of the required system output.
ENSURE AUTOMATIC OR MANUAL
7
Once started, record the time it takes for the motor to accelerate to what speed?
Full Speed
8
During the weekly inspection of the pump assembly, the fuel tank should be observed to be
two thirds full
9
According to Table 8.1.2 Summary of Fire Pumps Inspection, Testing and Maintenance, tank float switch is what type of inspection?
VISUAL AND TEST
10
The controller selector switch should be in the __________________________ position.
AUTO
11
During the weekly inspection of the pump assembly, the controller pilot should be
illuminated (power on)
12
During the weekly test of the fire pump assemblies, one must observe the time it takes for the motor to accelerate to __________________________.
FULL SPEED
13
The electrolyte level in the batteries should read?
NORMAL
14
Check valves _________________.
ALLOW WATER TO FLOW IN ONE DIRECTION
15
A weekly test of the fire pump assemblies shall be conducted
without flowing water
16
For both Electric & Diesel pumps, the wet pit suction screens should be?
UNOBSTRUCTED AND IN PLACE
17
The horizontal split case pump has a double suction impeller and is used with a positive suction supply. A variation of this design can be mounted in: A ____________________________________.
VERTICAL PLANE
18
What is a common cause of a pump to lose suction or fail to maintain its discharge pressure?
AIR DRAWN INTO SUCTION LINE THROUGH LEAKS
19
Pump packing boxes, bearings and casing shall be checked for ____________.
OVERHEATING
20
Types of centrifugal fire pumps include single and multistage units of horizontal and vertical shaft design.
True
21
The pump test shall be conducted by starting the pump automatically.
true
22
According to Table 8.1.2 Summary of Fire Pumps Inspection, Testing and Maintenance, oil level is what type of inspection? _______________
VISUAL AND CHECK
23
As observed during the weekly inspections, wet pit suction screens should be
unobstructed in place
24
The time controller is on first step ____________________________________________.
FOR REDUCED VOLTAGE OR REDUCED CURRENT STARTING
25
All alarm pilot lights should be in what state?
OFF
26
The most common cause of horizontal pump bearing failure, according to NFPA 25, is
STANDING WATER IN DRIP POCKETS
27
A gauge can be permitted to have a reading with an error of ________________ percent of the maximum full gauge reading.
+ OR – 3
28
A preventative maintenance program shall be established on all components of the pump assembly in accordance with:
MANUFACTURER’S RECOMMENDATIONS
29
At what level should the fuel tank be?
2/3
30
Which 5 pertinent visual observations specified in the NFPA 25 checklist that shall be performed weekly are (list all that apply)
pump house conditions, pump system conditions, electrical system conditions, diesel engine system conditions, steam system conditions
31
During the weekly inspection, the pump suction, discharge, and bypass valves should be observed to be ____.
fully open
32
When verifying the electrical system conditions, the controller pilot light should be?
GREEN
33
Regarding horizontal pumps, prior to operation, observe suction and discharge gauges. Readings higher than suction pressure indicate leakage back from system pressure through _________________.
EITHER FIRE PUMP OR JOCKEY PUMP
34
If a pump is operated without water in its casing, the wearing rings are likely to seize. The first warning is a change in ___________________________________________. Shut down the pump.
PACKING GLANDS NOT DRIPPING A ONE DROP PER SECOND
35
Increasing the engine speed beyond the rated speed of the pump at rated condition is an acceptable method for meeting the rated pump performance. ______________
False
36
Approximately how many drops per second is necessary to keep packing lubricated?
one
37
Controllers include ___________, ____________, or ____________operated units. Mark all that apply
AIR, ELECTRIC, HYDRAULIC
38
During the weekly inspection of the pump assembly, the reverse phase alarm pilot light should be observed to be
off
39
Reports: Any abnormality observed during inspection or testing shall be reported promptly to the
PROPERTY OWNER OR DESIGNATED REPRESENTATIVE
40
When verifying water level in suction reservoir during weekly inspection, the water level should be full.
true
41
Indicating valves provide a dependable _______________________________________, even at a distance.
VISABLE INDICATION OF THE OPEN POSITION
42
A weekly test of the Diesel fire pump assemblies shall be conducted by starting the pump without flowing water.
THE DIESEL PUMP SHALL BE RUN A MINIMUM OF 30 MINUTES
43
A vertical shaft, turbine-type pump is necessary where __________________________, such as from an underground reservoir, well, river or lake.
A SUCTION LIFT IS NEEDED
44
During the weekly inspection of the pump assembly, all Alarm pilot lights should be ________________.
off
45
All time delay intervals associated with the pump's STARTING, STOPPING AND ENERGY SOURCE TRANSFER shall be ___________________.
RECORDED
46
An impairment tag shall be posted at each fire department connection and system control valve indicating which system, or part thereof, has been removed from service.
true
47
A weekly fire pump test should be started automatically?
True
48
The isolating switch for electric pumps should be closed.
True
49
An automatic weekly test timer shall not be substituted for the normal starting procedure of the weekly test.
False
50
Before a horizontal pump is operated, check packing adjustment -approximately ______ drop(s) per second is necessary to keep packing lubricated
ONE
51
The preventive maintenance program shall be initiated _______________ after the pump assembly has passes acceptance tests.
IMMEDIATELY
52
The reverse phase alarm pilot light for electric pumps should be off.
True
53
At what level should the oil level in the vertical motor sight glass be?
ONE HALF SIGHT GLASS
54
Emergency impairments include system leakage, interruption of water supply, frozen or ruptured pipes, and ________.
equipment failures
55
During the weekly test of the fire pump assemblies, an installed safety relief valve shall ___________________________
PERMIT WATER TO FLOW
56
The normal life expectancy of a gauge is between
10-15 YEARS
57
Which is more important as it applies to water storage tanks or reservoirs for fire pump water supply: water level or water quality?
WATER LEVEL
58
During the weekly inspection, the suction reservoir should be observed to be
full
59
According to Table 8.1.2 Summary of Fire Pumps Inspection, Testing and Maintenance, inspecting fuel and water in a system is what type of inspection?
CHECK AND CLEAN
60
Weekly inspection requires verification that the pump suction discharge and bypass valves should be fully open?
TRUE
61
During the weekly inspection of the pump assembly, the oil level in the vertical motor sight glass should be observed to be
normal
62
A monthly test of the fire pump assemblies shall be conducted by starting the pump without flowing water. _____________________________________________
THE ELECTRIC PUMP SHALL BE RUN A MINIMUM OF 10 MINUTES
63
According to Table 8.1.2 Summary of Fire Pumps Inspection, Testing and Maintenance, cooling system, the condition of flexible hoses and connections is what type of inspection?
VISUAL AND CHECK
64
The purpose of inspecting the pump assembly is to
APPEARS TO BE IN OPERATING CONDITION AND IS FREE FROM PHYSICAL DAMAGE
65
The pertinent visual observation categories required to be inspected weekly checklists are? LIST ALL THAT APPLY
PUMP HOUSE CONDITIONS, PUMP SYSTEM CONDITIONS, ELECTRICAL SYSTEM CONDITIONS, DIESEL SYSTEM CONDITIONS, STEAM SYSTEM CONDITIONS
66
What can be substituted for the normal starting procedure of the weekly test of the fire pump assemblies?
AN AUTOMATIC WEEKLY TEST TIMER
67
During the weekly inspection of the pump assembly, the normal phase rotation pilot light should be observed to be
on
68
On diesel engines, if cooling water discharge is not adequate, check _______ for obstructions and adjust_______for correct flow.
strainer, pressure reducing valve
69
A horizontal split case pump has a _________________ with an inboard and outboard bearing and is used with a positive suction supply.
DOUBLE SUCTION IMPELLER
70
Minimum flow for a pump is the churn pressure. Peak flow for a fire pump is ________ PERCENT of the rated flow.
150
71
Automatic transfer switches shall be tested ROUTINELY and exercised in accordance with __________________________________.
NFPA 110
72
According to Table 8.1.2 Summary of Fire Pumps Inspection, Testing and Maintenance, cooling system, what type and frequency of inspection is done on the diesel engine, jacket water heater?
CHECK – WEEKLY
73
A vertical shaft turbine type pump is necessary where A SUCTION LIFT IS NEEDED, SUCH AS FROM AN ______________, _____________, _____________, OR ______________. List all apply.
UNDERGROUND RESERVOIR, WELL, RIVER, LAKE
74
During the weekly inspection of the pump assembly, the isolation switch should be observed to be
closed
75
The normal life expectancy of a gauge is between _______________ years.
10 & 15
76
What start method is required for the weekly fire pump test?
automatic
77
During the weekly check of the electrical system, what is recorded after starting the pump to check the automatic stop controller?
THE TIME PUMP RUNS AFTER STARTING
78
Regarding battery maintenance: An automatic battery charge is a substitute for proper maintenance of the battery and charger.
FALSE
79
There are two requirements listed under pump house conditions, choose both listed below.
VENTILATING LOUVERS ARE FREE TO OPERATE, ROOM TEMPERATURE CANNOT BE BELOW 40°F FOR DIESEL OPERATION
80
The weekly test pertinent adjustments shall be made while the pump is _________________________________.
RUNNING
81
The normal phase rotation pilot light should be on.
True
82
The fire pump shall be started manually for the test run.
False
83
Part of the check of the pump house conditions is that
ventilating louvers are free to operate
84
What fire pump type do you record the time to crank?
DIESEL
85
The number of engine operating hours is measured by the?
ENGINE RUNNING TIME METER
86
The oil level in the right-angle gear drive should be normal.
True
87
According to NFPA 25 California Edition, when an impeller is obstructed, it will not show on any one instrument, but pressures fall off rapidly when:
AN ATTEMPT IS MADE TO DRAW A LARGE AMOUNT OF WATER
88
The fire pump packing glands should have wht level of water discharge?
slight
89
A fire pump assembly provides __________ for private fire protection.
WATER FLOW AND PRESSURE
90
During the weekly inspection of the pump assembly, the electrolyte level in batteries should read _______.
normal
91
On horizontal pumps the difference between suction and discharge pressures should match ________ pressure as shown on the fire pump nameplate.
Churn
92
The transfer switch normal pilot light should be illuminated.
True
93
Backflow prevention devices are used to prevent water in a fire protection system from entering __________________________________________________, due to a reverse flow of water, thermal expansion, hydraulic shock, back pressure, or back siphonage.
THE PUBLIC WATER SUPPLY
94
Test results shall be recorded and retained for comparison purposes in accordance with Section 4.3.4 Original records shall be retained for __________________________
THE LIFE OF THE SYSTEM
95
Ball valves are manually operated through their full range of open to closed positions with ______________________________.
A ONE-QUARTER TURN
96
To check automatic stop controller, ______ is recorded after starting the pump.
time the pump runs after starting
97
Fuel maintenance: Fuel should be maintained free of water and foreign material by draining water and foreign material from the tank sump ______________________.
ANNUALLY
98
During the weekly inspection of the pump assembly, the oil level in the ____________ gear drive should be normal.
right angle
99
Diesel engine fuel tank level, float switch and solenoid valve operation shall be checked ____________________.
WEEKLY
100
The purpose of testing the pump assembly is to ensure automatic and manualoperation upon demand and Continuous delivery of the required __________________. An additional purpose is to detect ______.
SYSTEM OUTPUT, DEFICIENCIES NOT EVIDENT BY INSPECTION