  • 1

    Number of single compartment sinks or laundry tubs of the same depth, or lavatories that can be served by one trap

    3

  • 2

    Maximum center-to-center distance of adjacent fixtures being served by a single trap

    0.75m

  • 3

    Maximum length of tailpiece

    0.6m

  • 4

    Minimum horizontal distance of a trap arm to vent

    2x trap diameter

  • 5

    Trap arm change of direction without requiring a cleanout

    > 90°

  • 6

    For trap arms 75 mm Ø and larger, the change of direction not requiring a cleanout

    < 22 1/2°

  • 7

    Maximum developed length between the trap of a water closet from the top of closet ring to inner edge of vent

    1.8m

  • 8

    Minimum thickness of exposed and readily accessible drawn brass tubing trap

    GA 17 (1.1mm)

  • 9

    Maximum number of slip joints that may be used on the outlet side of a trap

    1

  • 10

    Depth of trap seals

    2" to 4"

  • 11

    Minimum water seal for sand interceptors and similar clarifiers

    152mm

  • 12

    Rate of flow of an individual grease trap

    1.3 to 3.4 L/s

  • 13

    The total capacity of fixtures discharging into a grease trap shall not exceed _____ times the flow rate of the grease trap

    2 1/2

  • 14

    Maximum number of fixtures connected to one grease trap

    4

  • 15

    Maximum horizontal distance between the fixture outlet and the grease trap, so grease trap may serve as fixture trap

    1.2m

  • 16

    Maximum vertical tailpiece or drain between the fixture outlet and the grease trap, so grease trap may serve as fixture trap.

    0.75m

  • 17

    Minimum water seal for grease trap

    51mm or 2"

  • 18

    Size of solids to be screened from laundry discharge by means of removable wire basket

    12.7mm or larger

  • 19

    Minimum outlet size of a sand interceptor

    76mm or 3"

  • 20

    Minimum net opening dimension of the inlet section of a sand interceptor

    0.2 sq.m

  • 21

    The minimum depth of sand interceptor under the invert of the outlet pipe

    610mm or 24"

  • 22

    Increase in the area of inlet section for each 18.9 LPM or fraction thereof over 75.7 LPM

    0.09 sq.m

  • 23

    Minimum area of sand interceptor outlet section

    50% of the inlet section

  • 24

    Distance of trap to vent for 32mm Ø

    762mm or 30" or 2.5'

  • 25

    Distance of trap to vent for 38mm Ø

    1067mm or 42" or 3.5'

  • 26

    Distance of trap to vent for 51mm Ø

    1524mm or 60" or 5'

  • 27

    Distance of trap to vent for 76mm Ø

    1829mm or 72" or 6'

  • 28

    Distance of trap to vent for 102mm Ø and larger

    3048mm or 120" or 10'

  • 29

    Maximum developed length between water closet and vent

    1829mm or 6'

  • 30

    Minimum thickness of galvanized sheet metal for rainwater downspout or conductor

    GA 26 (0.40mm)

  • 31

    Rainwater piping commencing ____ from the exterior of a building may be suitable approved materials

    0.6m or 2'

  • 32

    Extension of roof drain strainers above the surface of the roof

    102mm or 4"

  • 33

    Minimum total net inlet area of roof drain with dome-type strainers

    1.5x area of the outlet

  • 34

    Minimum total net inlet area of drain with roof deck strainers

    2x area of the outlet

  • 35

    Rainfall intensity normally used around Manila area

    102mm/hr

  • 36

    Additional for area of 1 wall

    50%

  • 37

    Additional for area of 2 adjacent walls

    35%

  • 38

    Additional for area of 2 opposite walls

    no additional area

  • 39

    Minimum diameter of building sewer, but not less than size of the building drain

    152mm or 6"

  • 40

    When gutter has semi-circular bottom, the depth of equivalent area of rectangular gutter

    0.392x diameter

  • 41

    When gutter has semi-circular bottom, width of equivalent area of rectangular gutter

    0.8862x diameter

  • 42

    The sizing data for vertical conductors, leaders, and drains is based on the pipes flowing ____ full

    7/24

  • 43

    Ratio of the side dimension of a rectangular vertical piping

    3:1

  • 44

    Public sewer is not available if more than

    61m

  • 45

    Minimum diameter of building sewer, but not less than the size of the building drain

    152mm or 6"

  • 46

    Recommended slope for building sewer

    2%

  • 47

    Allowable slope for drainage piping 102 mm or 152.4mm in diameter given the site constraints

    1%

  • 48

    Allowable slope for drainage piping 203 mm or larger in diameter

    0.5%

  • 49

    Distance of the building sewer from the outer face of any building foundation or wall

    0.6m or 2'

  • 50

    Minimum depth of building sewer below the finish surface of the ground

    0.3m or 1'

  • 51

    Aggregate offset angle to be provided with an additional cleanout

    135°

  • 52

    Length of building sewer not requiring for a cleanout

    < 3m

  • 53

    Maximum distance between manholes

    91m

  • 54

    Distance between bottom of water pipe and top of the sewer or drain line

    0.3m or 1'

  • 55

    Horizontal distance between the water line and the sewer or drain line

    0.3m or 1'

  • 56

    Distance between sewer or drainage piping and water pipes crossing above such drainage pipes

    0.3m or 1'

  • 57

    Minimum distance of water pipe joints away from a sewer line

    3m or 10'

  • 58

    Distance within the property line where every abandoned building sewer shall be plugged or capped

    1.5m or 5'

  • 59

    Maximum number of days from the time of connection to the public sewer an abandoned disposal facility shall be filled

    30 days

  • 60

    Minimum horizontal distance of a building or structure from the building sewer

    0.6m or 2'

  • 61

    Minimum horizontal distance of water supply wells from the building sewer

    15.2m

  • 62

    Minimum horizontal distance of streams from the building sewer.

    15.2m

  • 63

    Minimum horizontal distance of on-site domestic water service line from the building sewer

    0.3m or 1'

  • 64

    Minimum horizontal distance of public water main from the building sewer

    0.3m or 1'

  • 65

    Allowable reduction from water supply wells when constructed of approved materials for use within a building instead of 15.2m

    7.6m

  • 66

    Maximum/Minimum FU on 152mm building sewer @ 2%

    no minimum

  • 67

    Maximum/Minimum FU on 203mm building sewer @ 2%

    3900/275

  • 68

    Maximum/Minimum FU on 254mm building sewer @ 2%

    6800/300

  • 69

    Maximum/Minimum FU on 305mm building sewer @ 2%

    11200/235

  • 70

    Minimum depth to be filled with molten pig lead

    25.4mm

  • 71

    Extension of the finished joint below the rim of the hub

    3.2mm

  • 72

    Minimum wall thickness of threaded plastic pipe

    Schedule 80

  • 73

    Minimum thickness of exposed wiped surface on each side of a wiped joint, and at least as thick as the material being joined

    19mm

  • 74

    Maximum lead content allowable for solders and fluxes in potable water piping

    2%

  • 75

    Job-Fabricated female screws

    Schedule 80

  • 76

    Enlargement of closet bend from _____ shall be considered an obstruction

    76mm to 102mm

  • 77

    Minimum width of continuous and indelibly colored stripe marking for hard drawn copper tubing

    6.4mm

  • 78

    Green Copper Tubing

    Type K

  • 79

    Blue Copper Tubing

    Type L

  • 80

    Red Copper Tubing

    Type M

  • 81

    Yellow Copper Tubing

    Type DMV

  • 82

    Minimum weight and thickness of sheet lead for lead safe pans

    19.56 kg/sq. m.; 1.6 mm thick

  • 83

    Minimum weight and thickness of sheet lead for flashing or vent terminals

    14.63 kg/sq. m.; 1.2 mm thick

  • 84

    Minimum wall thickness of lead bends and lead traps

    3.2mm

  • 85

    Approximate diameter of closet rings or flanges

    178mm or 7"

  • 86

    Width of closet ring or flange

    38mm or 1 1/2"

  • 87

    Minimum thickness of caulked-on closet rings or flanges

    6.4mm

  • 88

    Minimum overall depth of caulked-on closet rings or flanges

    51mm or 2"

  • 89

    Number of bolts per water closet

    4

  • 90

    Slope of threaded-type drainage fittings

    2%

  • 91

    Sizes of valves that shall have cast iron bodies

    102mm or larger

  • 92

    Sizes of valves that shall have cast brass or bronze bodies

    less than 102mm

  • 93

    Sizes of valves that shall be brass and bronze metal

    up to 51mm