問題一覧
1
A special system discharging of a foam made from concentrates either mechanically or chemically over the area to provide protection
foam extinguishing system
2
A fire extinguishing system using one or more atoms of an element from the halogen chemical series fluorine, chlorine, bromine, and iodine
halogenated extinguishing system
3
An alarm caused by mechanical failure, malfunction, improper installation or lack of proper maintenance or an alarm activated by caused that cannot be determined
nuisance alarm
4
Standpipe system providing 2 1/2 inch (64mm) hose connections to supply water for use by fire departments and those trained for handling heavy fire streams
Class I System
5
Standpipe system providing 1 1/2 inch (38mm) hose connections to supply water for use of primarily by the building occupants or by fire department during initial response
Class II System
6
Standpipe system providing 1 1/2 inch (38mm) hose connections to supply water for use of primarily by the building occupants and 2 1/2 in (65mm) hose connection to supply larger volume of water for use by fire departments and those in handling heavy fire streams
Class III System
7
A solution of water and potassium-carbonate-based chemical, potassium-acetate-based chemical or a combination thereof fanning and extinguishing agent
Wet-Chemical extinguishing agent
8
A system or part of a system that can transmit and recieve signals without the aid of wire
Wireless protection system
9
A dry standpipe system that does not have permanent water supply attached to the system. It requires water from a fire department pumper to be pumped into the system through the fire department connection in order to supply the system demand
Manual Dry
10
A wet standpipe connected to a water supply for the purpose of maintaining water within the system but to which does not have a water supply capable of delivering the system demand attached to the system. It requires water from a fire department pumper (or that like) to be pumped into the system through the fire department connection in order to supply the system demand
Manual Wet
11
Sprinkler system shall have pressure zones
more than 175 psi
12
All structures occupied for the manufacture of storage of cellulose nitrate (pyroxylin) plastic shall be equipped with approved automatic fire extinguishing sprinkler system capable of discharging
1.66 gal/min/sq ft
13
Dry chemical extinguishing system shall be inspected for proper operation at how many months interval?
6 months
14
Foam extinguishing system shall be provided in buildings such as
maintenance aircraft hangars
15
Overhead foam-water sprinkler system proved closed foam water sprinkler in aircraft servicing area of minimum solution rate of
0.16 gal/min/sq ft of floor area
16
For wet pipe foam water sprinkler systems at what temperature is the sprinkler head quick response?
75 deg F
17
Carbon dioxide extinguishing system shall be inspected, tested for proper operation at how many months interval?
12 months interval
18
High pressure cylinders shall be weighed and the hydrostatic test shall be verified at
6 months interval
19
Dry standpipe (Class I or III) shall be limited to
8-storey building
20
Wet standpipe (Class I or III) shall be limited to
more than 8 storey building
21
Underground buildings shall be equipped throughout with what class automatic, wet or manual stand pipe?
Class I
22
Elevators are required for how many storey buildings
5 storey and above
23
A special system discharging a foam made from concentrates, either mechanically or chemically over the area to provide protection
Foam extinguishing system
24
A fire extinguishing system using one or more atoms of an element from the halogen chemical series fluorine, chlorine, bromine and iodine
Halogenated extinguishing system
25
Any flexible plan building or open plan building in which the travel distance of how many meters to exits must have approved and supervised sprinkler systems?
exceeds 46 m distance
26
All buildings shall be protected throughout by an approved supervised sprinkler system except in buildings where all guest suites door opening directly outside at the street or grade level or exterior exit access in buildings up to and including
3 storey in height
27
All business occupancy buildings over what height shall be provided with automatic sprinkler system?
15 m high
28
Fire extinguishers should be installed in plain view in an accessible spot near room exits which provides an escape route. It should be located away from fire hazards and installed at what height above the floor?
1500 mm
29
Sprinkler system shall have pressure zones so that sprinkler heads will not be subjected to pressure that is more than
175 psi
30
Carbon dioxide extinguishing system shall not be installed in areas normally occupied by
Persons (people)
31
The age limit of a horizontal return tubular, flue or cylinder boiler having a longitudinal lap joint and operating a pressure in excess of 0.345 MPa or 3.45 Bar gage shall be how many years?
30 years
32
When boilers are replaced or new boilers are installed in either existing or new buildings, a minimum height of at least how many mm shall be provided between the top of the boiler proper and the ceiling?
2130 mm
33
What is the minimum height from any highest spot of any valve stem and the ceiling for new boiler installation if it is a single installation or self contained boiler?
915 mm
34
A compressor or portion of a condensing unit supported from the ground shall rest on a concrete or other approved base extending ___ above the adjoining ground.
not less than 3 inches
35
Permanent gravity ventilation openings of _____ net free are opening directly to the outside of the building or extending to the outside of the building by continuous duct
not less than 2 ft^2
36
A mechanical exhaust system arranged to provide a complete change of air in such a room or space of at least every how many minutes to discharge to the outside of the building?
20 minutes
37
Ducting used for conveying air at temperatures not exceeding what temperature to or from occupied areas of any occupancy through other than heating or air conditioning systems such as ventilation for human usage, domestic kitchen range, exhaust, bathroom exhaust ducts and domestic type clothes dryer exhaust ducts?
121 deg C
38
Spaces provided with natural ventilation shall have a minimum permanent wall opening of how many percent of the net occupied area?
4%
39
For naturally ventilated spaces without direct wall opening to the outdoors except through adjoining rooms, the opening between rooms shall be permanently unobstructed and shall have free area of not less than how many percent of the occupied area?
8%
40
Determine the outdoor air rate required for a single zone AC unit serving an interior 2000ft^2 meeting/conference room with a design occupancy of 100 people. Note: the system supplies and returns are from the ceiling.
620 cfm
41
LPG are mixture of hydrocarbons liquefied under pressure for efficient transportation, storage and use. LPG are generally composed of Ethylene, Propane, Propylene, Butane, Isobutene and Butylenes. However commercially they are classified as mixtures of
Propane and Butane
42
It is defined as a petroleum distillate having a flash point not below 22.8 C as determined by Abel tested which is equivalent to 22.8 C as an illuminant when burned in a wick lamp
Kerosene
43
Which of the following mixture of air and gasoline vapors are explosive?
1.3% to 6.0%
44
It is a solid, infusible, cellular residue left after fusible bitum coals are heated in the abscence of air, above temperature of which active thermal composition of the coal occurs
coke
45
They are frequently described as "Paraffinic" , "napthalenic mixed base" according to the physical characteristics
Crude oils
46
Standard railings shall be at least what height from the outer surface of the top of the rail to the floor level?
atleast 1000 mm
47
Work rooms (referring to maintenance shop and machine room) shall be at what height from the floor to ceiling?
atleast 3000 mm
48
The maximum number of persons working or will be working not exceed 1 person per how many square meters?
12
49
Foundation mass should be how many times the weight of machinery. It is supposed to support if the unbalance foundation produced by the machine can be calculated to dampen vibration.
10 to 20 times
50
The weight of the machine plus the weight of the foundation should be distributed over a sufficient soil area which is enough to cause a bearing stress with safe bearing capacity. The soil with factor of safety equivalent to:
5
51
Machine foundation should be isolated from floor slab building footings at what distance around its perimeter. Eliminate transmission of vibration
25 mm
52
Foundation bolts of specified size should be used surrounded by a pipe sleeve with an inside diameter of atleast how many times the diameter of anchor bolt
3 times
53
The person responsible for the maintenance of a particular fire protection alarm
impairment coordinator
54
Foundation mass should be how many times the weight of machinery it is supposed to support?
3 to 5 times