    The developed length between the trap of a water closet or similar fixture measured from the top of closet ring (closet flange) to inner edge of vent shall not exceed _____ m.

    1.8

  • 2

    Interceptors for sand and similar heavy solids shall have a water seal of not less than _____ mm deep.

    152

  • 3

    The sand interceptor shall have a minimum dimension of _____ m^2 for the net free opening of the inlet section.

    0.2

  • 4

    No standpipe receptor for any clotheswasher shall extend more than _____ m nor less than 0.45 m above its trap.

    0.8

  • 5

    Estimated sewage flow rate for Day Camps (no meals served)

    56.8 LpD

  • 6

    Interceptors shall be of approved design and be of not less than _____ compartments

    2

  • 7

    Lead pipe shall be supported at intervals not exceeding _____ m at centers with a rigid vertical back-up.

    1.2

  • 8

    A _____ kpa air pressure may be substituted for the water test.

    344.5

  • 9

    No part of the perimeter of the leaching bed shall be more than ____ from a distribution drain line.

    0.9 m

  • 10

    When disposal fields are installed, a minimum of _____ of trench bottom shall be provided for each system exclusive of any hard pan, rock, clay, or other impervious formations.

    14 sqm

  • 11

    Minimum thickness of lead safe pan in mm

    1.6

  • 12

    The corresponding maximum trap loading pipe size for fixture unit 6 (answer in mm)

    76

  • 13

    The arch or dome of seepage pit shall be an approved type one or two piece reinforced concrete slab of ____ minimum compressive strength.

    2500 psi

  • 14

    The width of a continuous and indelibly colored stripe in copper tubing.

    6.4 mm

  • 15

    Closet rings shall be tightly fastened with corrosive resistant fasteners up to the floor with top surface _____ mm above finish floor.

    6.4

  • 16

    Estimated sewage flow rate for airports per employee

    56.8 LpD

  • 17

    Cleanouts may be omitted on a horizontal drain line less than _____ m in length unless such line is serving sinks or urinals

    1.5

  • 18

    The public sewer may be considered as not being available when such public sewer or any exterior drainage facility connected thereto is located more than _____ m from any proposed building or exterior drainage facility on any lot or premises thereat.

    61

  • 19

    The diameter of an individual vent shall not be less than _____ mm nor less than 1/2 the diameter of the drain to which it is connected.

    32

  • 20

    Each pressure relief valve shall be an approved automatic type with drain and each such relief valve shall be set at a pressure of not more than _____ kpa

    1033

  • 21

    Tunnels shall have a clear height of _____ m above the pipe and shall be limited in length to 1/2 the depth of trench, with a maximum length of 2.4 meters.

    0.6 m

  • 22

    Trenches shall be back-filled in thin layers of _____ m.

    0.3

  • 23

    Each run of pipe which is more than _____ m in total developed length shall be provided with a cleanout.

    15

  • 24

    Every abandoned building (house) sewer, or part thereof, shall be plugged or capped in an approved manner within _____ m of the property line.

    1.5

  • 25

    Lead bends and lead traps shall not be less than ____ mm in wall thickness.

    3.2

  • 26

    Limit stops shall be provided on such valves and shall be adjusted to deliver hot water with a maximum temperature of _____ deg. C

    48.8

  • 27

    (Vertical wall areas for rainwater piping size) For two adjacent walls, add _____ percent of the total wall areas to the roof area.

    35

  • 28

    If the highest group of the fixtures contains flushometer valves , the pressure for the group should not be less than _____.

    103.42 kpa

  • 29

    Each seepage pit shall have a minimum sidewall of _____ below the inlet.

    3 m

  • 30

    Each vent pipe or stack through roof shall extend its flashing all around and the stack vent shall terminate vertically not less than _____ m above the roof.

    0.15

  • 31

    The yoke vent connection with the vent stack shall be placed not less than _____ m above the floor level.

    1

  • 32

    An additional cleanout shall be provided on a horizontal line with an aggregate offset angle of direction exceeding _____ degrees.

    135

  • 33

    (Septic Tank) The liquid depth shall be not less than ______ nor more than _____.

    0.6 m to 1.8 m

  • 34

    Distance of Building or structures to Building Sewer (answer in meters)

    0.60 m

  • 35

    Storage factor for fully equipped commercial kitchen- 16 hours operation

    2

  • 36

    Backflow prevention for hot water over ____ deg. C shall be a listed type assembly.

    43.3

  • 37

    Water pipes crossing sewer or drainage piping constructed of clay or materials, not approved for use within a building, shall be laid a minimum of _____ m above the sewer or drainpipe.

    0.3

  • 38

    No galvanized wrought iron or galvanized steel pipe shall be used underground and shall be kept at least _____ mm above ground.

    152

  • 39

    When the quantity of sewage exceeds the amount that can be disposed in a _____ meter of each line, a dosing tank shall be used.

    152.4 m

  • 40

    457.2 m

    34.5

  • 41

    The water shall be kept in the pipe system or in the portion under test for at least _____ minutes before inspection starts.

    15

  • 42

    Allowable slope of a pipe having a diameter 203 mm or larger is _____%.

    0.5

  • 43

    Fixture outlets shall not be connected to the horizontal excreta drainage piping system within _____ m of any vertical to horizontal change of direction of a stack containing suds-producing fixtures.

    2.4

  • 44

    No underfloor cleanout in any residential occupancy shall be located more than _____ m from an access door, trap door or crawl hole.

    6.1

  • 45

    For flush tank supplies, the available pressure may not be less than _____.

    55.16 kpa

  • 46

    Depth of equivalent area of rectangular gutter = ____ x diameter.

    0.392

  • 47

    Retention time of commercial kitchen waste

    2.5 hours

  • 48

    Fixtures that also serves as a vent for not to exceed _____ fixtures.

    4

  • 49

    The distance to vent of a trap arm 51 mm in diameter. (answer in meters)

    1.52

  • 50

    Where the local water pressure is in excess of _____ kpa, an approved-type pressure regulator preceded by an adequately sized strainer shall be installed to reduce the pressure on the building side of the regulator to the required supply pressure.

    551

  • 51

    The corresponding maximum trap loading pipe size for fixture unit 3 (answer in mm)

    38

  • 52

    An exposed and readily accessible drawn brass tubing trap, not less than Gauge ___ may be used on fixtures discharging domestic sewage but shall exclude urine.

    17

  • 53

    Distribution drain lines in leaching beds shall be more than ____ apart on centers.

    1.8 m

  • 54

    Each grease trap shall have an approved water seal of not less than _____ mm.

    51

  • 55

    Cleanout size of 64 mm pipe. (answer in mm)

    64

  • 56

    Each vent opening shall terminate not less than _____ m above any openable window, door opening, air intake or vent shaft.

    0.9

  • 57

    Wiped lead joints shall have an exposed surface on each side of a joint not less than _____ mm.

    19

  • 58

    Cast iron fittings up to and including _____ mm in size when used in connection with potable water piping shall be galvanized.

    51

  • 59

    In a water test, each section shall be filled with water, but no section shall be tested with less than _____ m head of water.

    3

  • 60

    The minimum size of any pump discharge or any discharge pipe from a sump having a water closet connected thereto shall not be less than _____ mm diameter.

    50.8

  • 61

    Distance of Septic Tank to to Water Supply wells.

    15.2 m

  • 62

    The inlet compartment of any septic tank shall be not less than _____ of the total capacity of the tank.

    2/3

  • 63

    When disposal fields and/or seepage pits are installed in sloping ground, the minimum horizontal distance between any part of the leaching system and ground surface shall be _____.

    4.6 m

  • 64

    The minimum wall thickness of any steel tank shall be _____ mm.

    2.8 mm

  • 65

    How many tests cocks does a Double Check Valve Backflow Prevention Assembly have?

    4

  • 66

    Vertical vent pipes for outdoor installations shall extend to at least _____ m distant from any part of the roof that is used for other purposes.

    3

  • 67

    Water closets shall be computed as _____ fixture units when determining septic tank size.

    6

  • 68

    Access to each septic tank shall be provided by at least two manholes _____ in minimum dimension.

    508 mm

  • 69

    Side walls of the septic tank shall exceed at least _____ above the liquid depth.

    228.6 mm

  • 70

    Support trap arms in excess of _____ feet in length as close as possible to the trap.

    3

  • 71

    Restaurant kitchen and other special-use sinks may be made of approved-type bonderized and galvanized sheet steel of not less than Gauge No. _____.

    16

  • 72

    Water pipes and fittings with a lead content that exceed ___% shall be prohibited and not used in potable piping systems.

    8

  • 73

    Water pipe joints shall be installed not less than _____ m away from sewer line in both directions.

    3

  • 74

    Such tailpiece or connections shall be as short as possible and in no case shall exceed _____ m long.

    0.6

  • 75

    Before placing filter material or drain lines in a prepared excavation, all smeared or compacted surfaces shall be removed from trenches by raking to a depth of _____ mm.

    25.4 mm

  • 76

    All septic tank covers shall be capable of supporting an earth load of not less than _____ when the maximum coverage does not exceed 9m.

    14.4 kpa

  • 77

    Where there is exposure to skin contamination with poisonous, infectious, or irritating materials, provide 1 lavatory for each _____ persons.

    5

  • 78

    Minimum depth of filter materials under drain lines

    304.8 mm

  • 79

    When seepage pits are used in combination with disposal fields, the filter material in the trenches shall terminate at least _____ from the pit excavation.

    1.5 m

  • 80

    The vacuum breaker shall be installed at the discharge side of the flushometer valve with the critical level at least _____ mm.

    152

  • MT 6

    MT 6

    ユーザ名非公開 · 49問 · 9日前

    MT 6

    MT 6

    49問 • 9日前
    ユーザ名非公開

    Plumbing Code WSFU

    Plumbing Code WSFU

    Vaantoote · 58問 · 1年前

    Plumbing Code WSFU

    Plumbing Code WSFU

    58問 • 1年前
    Vaantoote

    問題一覧

  • 1

    The developed length between the trap of a water closet or similar fixture measured from the top of closet ring (closet flange) to inner edge of vent shall not exceed _____ m.

    1.8

  • 2

    Interceptors for sand and similar heavy solids shall have a water seal of not less than _____ mm deep.

    152

  • 3

    The sand interceptor shall have a minimum dimension of _____ m^2 for the net free opening of the inlet section.

    0.2

  • 4

    No standpipe receptor for any clotheswasher shall extend more than _____ m nor less than 0.45 m above its trap.

    0.8

  • 5

    Estimated sewage flow rate for Day Camps (no meals served)

    56.8 LpD

  • 6

    Interceptors shall be of approved design and be of not less than _____ compartments

    2

  • 7

    Lead pipe shall be supported at intervals not exceeding _____ m at centers with a rigid vertical back-up.

    1.2

  • 8

    A _____ kpa air pressure may be substituted for the water test.

    344.5

  • 9

    No part of the perimeter of the leaching bed shall be more than ____ from a distribution drain line.

    0.9 m

  • 10

    When disposal fields are installed, a minimum of _____ of trench bottom shall be provided for each system exclusive of any hard pan, rock, clay, or other impervious formations.

    14 sqm

  • 11

    Minimum thickness of lead safe pan in mm

    1.6

  • 12

    The corresponding maximum trap loading pipe size for fixture unit 6 (answer in mm)

    76

  • 13

    The arch or dome of seepage pit shall be an approved type one or two piece reinforced concrete slab of ____ minimum compressive strength.

    2500 psi

  • 14

    The width of a continuous and indelibly colored stripe in copper tubing.

    6.4 mm

  • 15

    Closet rings shall be tightly fastened with corrosive resistant fasteners up to the floor with top surface _____ mm above finish floor.

    6.4

  • 16

    Estimated sewage flow rate for airports per employee

    56.8 LpD

  • 17

    Cleanouts may be omitted on a horizontal drain line less than _____ m in length unless such line is serving sinks or urinals

    1.5

  • 18

    The public sewer may be considered as not being available when such public sewer or any exterior drainage facility connected thereto is located more than _____ m from any proposed building or exterior drainage facility on any lot or premises thereat.

    61

  • 19

    The diameter of an individual vent shall not be less than _____ mm nor less than 1/2 the diameter of the drain to which it is connected.

    32

  • 20

    Each pressure relief valve shall be an approved automatic type with drain and each such relief valve shall be set at a pressure of not more than _____ kpa

    1033

  • 21

    Tunnels shall have a clear height of _____ m above the pipe and shall be limited in length to 1/2 the depth of trench, with a maximum length of 2.4 meters.

    0.6 m

  • 22

    Trenches shall be back-filled in thin layers of _____ m.

    0.3

  • 23

    Each run of pipe which is more than _____ m in total developed length shall be provided with a cleanout.

    15

  • 24

    Every abandoned building (house) sewer, or part thereof, shall be plugged or capped in an approved manner within _____ m of the property line.

    1.5

  • 25

    Lead bends and lead traps shall not be less than ____ mm in wall thickness.

    3.2

  • 26

    Limit stops shall be provided on such valves and shall be adjusted to deliver hot water with a maximum temperature of _____ deg. C

    48.8

  • 27

    (Vertical wall areas for rainwater piping size) For two adjacent walls, add _____ percent of the total wall areas to the roof area.

    35

  • 28

    If the highest group of the fixtures contains flushometer valves , the pressure for the group should not be less than _____.

    103.42 kpa

  • 29

    Each seepage pit shall have a minimum sidewall of _____ below the inlet.

    3 m

  • 30

    Each vent pipe or stack through roof shall extend its flashing all around and the stack vent shall terminate vertically not less than _____ m above the roof.

    0.15

  • 31

    The yoke vent connection with the vent stack shall be placed not less than _____ m above the floor level.

    1

  • 32

    An additional cleanout shall be provided on a horizontal line with an aggregate offset angle of direction exceeding _____ degrees.

    135

  • 33

    (Septic Tank) The liquid depth shall be not less than ______ nor more than _____.

    0.6 m to 1.8 m

  • 34

    Distance of Building or structures to Building Sewer (answer in meters)

    0.60 m

  • 35

    Storage factor for fully equipped commercial kitchen- 16 hours operation

    2

  • 36

    Backflow prevention for hot water over ____ deg. C shall be a listed type assembly.

    43.3

  • 37

    Water pipes crossing sewer or drainage piping constructed of clay or materials, not approved for use within a building, shall be laid a minimum of _____ m above the sewer or drainpipe.

    0.3

  • 38

    No galvanized wrought iron or galvanized steel pipe shall be used underground and shall be kept at least _____ mm above ground.

    152

  • 39

    When the quantity of sewage exceeds the amount that can be disposed in a _____ meter of each line, a dosing tank shall be used.

    152.4 m

  • 40

    457.2 m

    34.5

  • 41

    The water shall be kept in the pipe system or in the portion under test for at least _____ minutes before inspection starts.

    15

  • 42

    Allowable slope of a pipe having a diameter 203 mm or larger is _____%.

    0.5

  • 43

    Fixture outlets shall not be connected to the horizontal excreta drainage piping system within _____ m of any vertical to horizontal change of direction of a stack containing suds-producing fixtures.

    2.4

  • 44

    No underfloor cleanout in any residential occupancy shall be located more than _____ m from an access door, trap door or crawl hole.

    6.1

  • 45

    For flush tank supplies, the available pressure may not be less than _____.

    55.16 kpa

  • 46

    Depth of equivalent area of rectangular gutter = ____ x diameter.

    0.392

  • 47

    Retention time of commercial kitchen waste

    2.5 hours

  • 48

    Fixtures that also serves as a vent for not to exceed _____ fixtures.

    4

  • 49

    The distance to vent of a trap arm 51 mm in diameter. (answer in meters)

    1.52

  • 50

    Where the local water pressure is in excess of _____ kpa, an approved-type pressure regulator preceded by an adequately sized strainer shall be installed to reduce the pressure on the building side of the regulator to the required supply pressure.

    551

  • 51

    The corresponding maximum trap loading pipe size for fixture unit 3 (answer in mm)

    38

  • 52

    An exposed and readily accessible drawn brass tubing trap, not less than Gauge ___ may be used on fixtures discharging domestic sewage but shall exclude urine.

    17

  • 53

    Distribution drain lines in leaching beds shall be more than ____ apart on centers.

    1.8 m

  • 54

    Each grease trap shall have an approved water seal of not less than _____ mm.

    51

  • 55

    Cleanout size of 64 mm pipe. (answer in mm)

    64

  • 56

    Each vent opening shall terminate not less than _____ m above any openable window, door opening, air intake or vent shaft.

    0.9

  • 57

    Wiped lead joints shall have an exposed surface on each side of a joint not less than _____ mm.

    19

  • 58

    Cast iron fittings up to and including _____ mm in size when used in connection with potable water piping shall be galvanized.

    51

  • 59

    In a water test, each section shall be filled with water, but no section shall be tested with less than _____ m head of water.

    3

  • 60

    The minimum size of any pump discharge or any discharge pipe from a sump having a water closet connected thereto shall not be less than _____ mm diameter.

    50.8

  • 61

    Distance of Septic Tank to to Water Supply wells.

    15.2 m

  • 62

    The inlet compartment of any septic tank shall be not less than _____ of the total capacity of the tank.

    2/3

  • 63

    When disposal fields and/or seepage pits are installed in sloping ground, the minimum horizontal distance between any part of the leaching system and ground surface shall be _____.

    4.6 m

  • 64

    The minimum wall thickness of any steel tank shall be _____ mm.

    2.8 mm

  • 65

    How many tests cocks does a Double Check Valve Backflow Prevention Assembly have?

    4

  • 66

    Vertical vent pipes for outdoor installations shall extend to at least _____ m distant from any part of the roof that is used for other purposes.

    3

  • 67

    Water closets shall be computed as _____ fixture units when determining septic tank size.

    6

  • 68

    Access to each septic tank shall be provided by at least two manholes _____ in minimum dimension.

    508 mm

  • 69

    Side walls of the septic tank shall exceed at least _____ above the liquid depth.

    228.6 mm

  • 70

    Support trap arms in excess of _____ feet in length as close as possible to the trap.

    3

  • 71

    Restaurant kitchen and other special-use sinks may be made of approved-type bonderized and galvanized sheet steel of not less than Gauge No. _____.

    16

  • 72

    Water pipes and fittings with a lead content that exceed ___% shall be prohibited and not used in potable piping systems.

    8

  • 73

    Water pipe joints shall be installed not less than _____ m away from sewer line in both directions.

    3

  • 74

    Such tailpiece or connections shall be as short as possible and in no case shall exceed _____ m long.

    0.6

  • 75

    Before placing filter material or drain lines in a prepared excavation, all smeared or compacted surfaces shall be removed from trenches by raking to a depth of _____ mm.

    25.4 mm

  • 76

    All septic tank covers shall be capable of supporting an earth load of not less than _____ when the maximum coverage does not exceed 9m.

    14.4 kpa

  • 77

    Where there is exposure to skin contamination with poisonous, infectious, or irritating materials, provide 1 lavatory for each _____ persons.

    5

  • 78

    Minimum depth of filter materials under drain lines

    304.8 mm

  • 79

    When seepage pits are used in combination with disposal fields, the filter material in the trenches shall terminate at least _____ from the pit excavation.

    1.5 m

  • 80

    The vacuum breaker shall be installed at the discharge side of the flushometer valve with the critical level at least _____ mm.

    152